2004-01-06 00:00:00DENIED:
 RETURN AIR JUMPER FROM THE MASTER
 BEDROOM IS NOT SIZED PROPERLY.ALL AIR
 TO THE MASTER SUITE IS TO BE INCLUDED IN
 THE CALCULATION FOR TOTAL SUPPLY AIR.
 RETURN AIR SHALL BE SIZED ACCORDING TO
 THE TOTAL OF SUPPLY AIR. SEE ATTACHED
 SCHEDULE & REVISE ACCORDINGLY.
  