2004-01-09 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-STORM SHUTTERS: A)REVISE KEY PLAN AND
 INSTALLATION SCHEDULE. NEED EMERGENCY
 EGRESS THAT COMPLIES WITH SECTION
 1005.4.5 FBC 2001.
 B)CLEARLY MARK ON SHUTTERS DWGS SPECIFIC
 ANCHOR & SPACING TO BE USED ACCORDING
 TO MOUNTING CONDITIONS, EDGE DISTANCE,
 PANEL SPAN, CONNECTION TYPE AND THE
 STRUCTURE TO BE ATTACHED TO (MASONRY
 OR CONCRETE). SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR:
 A)HORIZONTAL SLIDER WINDOW: NEED THE
 APPROVED DRAWINGS.
 B)GLASS BLOCK.
 C)ROOF TILE (FBC APPROVAL IS PENDING).
 D)SINGLE HUNG WINDOWS.
 E)ENTRY DOOR WITH SIDELITE ASSEMBLY.
 F)SLIDING GLASS DOORS.
 G)WINDOW MULLIONS.
  
 4-ARCHITECT TO HAVE ALL HIS INFORMATION
 ON TITLE BLOCK AS REQUIRED BY CHAPTER
 481 FL STATUTES. SEE FAC SECTION
 61G1-16.004.
 **NOTE: THIS COMMENT HAVE BEEN ADDRESSED
 BEFORE SEVERAL TIMES AND STILL IS
 NOT DONE.
 5- 1 HR. FIRE RATED GLASS BLOCK ASSEMBLY
 NEED SPECIFIC UL LISTED ASSEMBLY AND
 REVISE DETAIL TO MATCH SUCH ASSEMBLY.
 SPECIFY ALL COMPONENTS THAT MAKE THE
 ONE HR. FIRE RATED ASSEMBLY.SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 6-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL
 E/4 AND NOTES ON DWG #2 DON'T MATCH.
 CHECK SIZE OF FASTENER. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC 2001.
 B)SPECIFY USP RT SIZES TO VERIFY VALUE
 SPECIFIED ON CATALOGUE.
 NOTE: PROVIDE ENGINEERING CALCS FOR
 VALUES OTHER THAN THOSE PUBLISHED ON
 CATALOGUE. SECTION 104.2.1.2 OF CITY
 AMENDMENTS TO FBC 2001.
 8-ENGINEER TO SPECIFY ROOF TILE FASTENER
 AS REQ'D BY SEC. 104.2.1.1OF CITY
 AMENDMENTS TO FBC 2001.
 9-REVISE WINDOW/DOOR BUCK DETAIL. SEE
 SEC. 1707.4.4.2 FBC 2001 FOR PROPER
 BUCK INSTALLATION.
 10-CLARIFY WHERE IS CONNECTOR USP
 EHUH 28-3 TAKEN FROM?. INABLE TO FIND
 ON USP CATALOGUE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 11-SHEET #7:A)MISSING CONNECTOR AT ONE
 END OF GIRDER TRUSS AT PORCH. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)REAR ELEVATION: CLARIFY WHY DESIGN
 PRESSURES ARE THE SAME, EVEN FOR OPG'S
 BIGGER THAN OTHERS. REVISE AS REQ'D.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 659-8096.