2004-01-09 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-STORM SHUTTERS: A)REVISE KEY PLAN AND |
| INSTALLATION SCHEDULE. NEED EMERGENCY |
| EGRESS THAT COMPLIES WITH SECTION |
| 1005.4.5 FBC 2001. |
| B)CLEARLY MARK ON SHUTTERS DWGS SPECIFIC |
| ANCHOR & SPACING TO BE USED ACCORDING |
| TO MOUNTING CONDITIONS, EDGE DISTANCE, |
| PANEL SPAN, CONNECTION TYPE AND THE |
| STRUCTURE TO BE ATTACHED TO (MASONRY |
| OR CONCRETE). SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR: |
| A)HORIZONTAL SLIDER WINDOW: NEED THE |
| APPROVED DRAWINGS. |
| B)GLASS BLOCK. |
| C)ROOF TILE (FBC APPROVAL IS PENDING). |
| D)SINGLE HUNG WINDOWS. |
| E)ENTRY DOOR WITH SIDELITE ASSEMBLY. |
| F)SLIDING GLASS DOORS. |
| G)WINDOW MULLIONS. |
| |
| 4-ARCHITECT TO HAVE ALL HIS INFORMATION |
| ON TITLE BLOCK AS REQUIRED BY CHAPTER |
| 481 FL STATUTES. SEE FAC SECTION |
| 61G1-16.004. |
| **NOTE: THIS COMMENT HAVE BEEN ADDRESSED |
| BEFORE SEVERAL TIMES AND STILL IS |
| NOT DONE. |
| 5- 1 HR. FIRE RATED GLASS BLOCK ASSEMBLY |
| NEED SPECIFIC UL LISTED ASSEMBLY AND |
| REVISE DETAIL TO MATCH SUCH ASSEMBLY. |
| SPECIFY ALL COMPONENTS THAT MAKE THE |
| ONE HR. FIRE RATED ASSEMBLY.SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 6-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL |
| E/4 AND NOTES ON DWG #2 DON'T MATCH. |
| CHECK SIZE OF FASTENER. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 7-REVISE/UPDATE TRUSS ANCHOR SCHEDULE & |
| ALL DETAILS THAT ARE AFFECTED BY SEC. |
| 1609.4.3 FBC 2001. |
| B)SPECIFY USP RT SIZES TO VERIFY VALUE |
| SPECIFIED ON CATALOGUE. |
| NOTE: PROVIDE ENGINEERING CALCS FOR |
| VALUES OTHER THAN THOSE PUBLISHED ON |
| CATALOGUE. SECTION 104.2.1.2 OF CITY |
| AMENDMENTS TO FBC 2001. |
| 8-ENGINEER TO SPECIFY ROOF TILE FASTENER |
| AS REQ'D BY SEC. 104.2.1.1OF CITY |
| AMENDMENTS TO FBC 2001. |
| 9-REVISE WINDOW/DOOR BUCK DETAIL. SEE |
| SEC. 1707.4.4.2 FBC 2001 FOR PROPER |
| BUCK INSTALLATION. |
| 10-CLARIFY WHERE IS CONNECTOR USP |
| EHUH 28-3 TAKEN FROM?. INABLE TO FIND |
| ON USP CATALOGUE. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 11-SHEET #7:A)MISSING CONNECTOR AT ONE |
| END OF GIRDER TRUSS AT PORCH. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| B)REAR ELEVATION: CLARIFY WHY DESIGN |
| PRESSURES ARE THE SAME, EVEN FOR OPG'S |
| BIGGER THAN OTHERS. REVISE AS REQ'D. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT 659-8096. |