Plan Review Notes For Permit 03121470 |
Permit Number |
03121470 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-03-09 00:00:00 | PROVISO: | | PLAN SUBMITTED FOR RESTAMP IS NOT THE | | SAME AS THE APPROVED SET OF PLANS.THE | | RETURN AIR JUMPER FROM THE MASTER | | BEDROOM & BEDROOM #3 ARE NOT SIZED | | PROPERLY.THE RETURN FOR THE MASTER | | BEDROOM SHALL BE A MINIMUM OF 14" & | | BEDROOM #3 SHALL BE A MINIMUM OF 9". | | | | SUBMITTED A REVISED MECHANICAL PLAN | | SHOWING PROPER SIZE FOR THE | | AFOREMENTIONED ROOMS PRIOR TO FINAL | | INSPECTION. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|