Date |
Text |
2004-01-23 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-SOME DRAWINGS ARE MISSING INFORMATION |
| REQUIRED BY ARCHITECT TO BE INCLUDED |
| IN ALL PLANS. CHAPTER 481 FL STATUTES. |
| NAME OF ARCHITECT AND DATE OF SEALING. |
| 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| PRODUCT APPROVAL FOR WINDOWS, DOORS, |
| GLASS BLOCK, ROOF TILE, MULLIONS AND |
| STRUCTURAL CONNECTORS. |
| 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| DON'T MATCH. CHECK FASTENER SIZE. |
| 4-TRUSS ANCHOR SCHEDULE: PROVIDE CALCS |
| FOR TYPE/NUMBER OF FASTENERS OTHER |
| THAN THOSE TESTED AND PUBLISHED BY USP |
| TO COMPLY WITH SEC. 1609.4.3 FBC 2001. |
| 5-DESIGNER OF RECORD TO SPECIFY ROOF |
| TILE FASTENERS. SEC. 104.2.1.1 CITY |
| AMENDMENTS TO FBC 2001 AND SECTION |
| 1606.3 FBC 2001. |
| 6-REVISE WINDOW BUCK DTAIL. SEE SECTION |
| 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| INSTALLATION. |
| 7-SHEET #3: A)REVISE/CLARIFY EXTERIOR |
| OPENING DESIGN PRESSURES ACCORDING TO |
| SIZE AND LOCATION. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| B)PROVIDE ENGINEERING CALCS FOR SYMPSON |
| EG7 CONNECTOR FASTENERS, SINCE THEY'RE |
| DIFFEENT THAN THOSE TESTED & PUBLISHED |
| TO COMPLY WITH SEC. 1609.4.3 FBC 2001. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC |