Plan Review Notes
Plan Review Notes For Permit 03121470
Permit Number 03121470
Review Stop B
Sequence Number 2
Notes
Date Text
2004-01-23 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-SOME DRAWINGS ARE MISSING INFORMATION
 REQUIRED BY ARCHITECT TO BE INCLUDED
 IN ALL PLANS. CHAPTER 481 FL STATUTES.
 NAME OF ARCHITECT AND DATE OF SEALING.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR WINDOWS, DOORS,
 GLASS BLOCK, ROOF TILE, MULLIONS AND
 STRUCTURAL CONNECTORS.
 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK FASTENER SIZE.
 4-TRUSS ANCHOR SCHEDULE: PROVIDE CALCS
 FOR TYPE/NUMBER OF FASTENERS OTHER
 THAN THOSE TESTED AND PUBLISHED BY USP
 TO COMPLY WITH SEC. 1609.4.3 FBC 2001.
 5-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001 AND SECTION
 1606.3 FBC 2001.
 6-REVISE WINDOW BUCK DTAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 7-SHEET #3: A)REVISE/CLARIFY EXTERIOR
 OPENING DESIGN PRESSURES ACCORDING TO
 SIZE AND LOCATION. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 B)PROVIDE ENGINEERING CALCS FOR SYMPSON
 EG7 CONNECTOR FASTENERS, SINCE THEY'RE
 DIFFEENT THAN THOSE TESTED & PUBLISHED
 TO COMPLY WITH SEC. 1609.4.3 FBC 2001.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC