Plan Review Notes
Plan Review Notes For Permit 03121470
Permit Number 03121470
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-15 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO COMPLY WITH ALL REQUIRE-
 MENTS OF CHAPTER 481 FLORIDA STATUTES
 WHEN SUBMITTING DWGS FOR PUBLIC RECORD
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: ALL DOORS/WINDOW
 TYPE, GLASS BLOCK MULLIONS, ROOF TILE
 AND STRUCTURAL CONNECTORS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL TO MATCH AL COMPONENTS
 ON SUCH ASSEMBLY. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK FASTENER SIZE.
 6-A)UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS THAT ARE AFFECTED BY SECTION
 1609.4.3 FBC REGARDING STEEL STRESS.
 NEED ENGINEERING CALCS FOR DIFFERENT
 VALUES AND FASTENERS OTHER THAN THOSE
 PUBLISHED ON REVISED CATALOGUES.
 B)SPECIFY SIZE OF USP RT STRAPS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-A)DESIGN PRESSURES FOR EXTERIOR OPG'S
 DON'T MATCH TABLES 1606.2B & 1606.2E
 FBC 2001 ACCORDING TO SIZE/LOCATION.
 PROVIDE CALCULATIONS FOR PRESSURES
 THAT AREN'T CLOSE TO ABOVE TABLES. SEC
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)PROVIDE CALCULATIONS TO SHOW SIMPSON
 EG-7 CONNECTOR COMPLIANCE WITH SECTION
 1609.4.3 FBC 2001 SINCE FASTENERS ARE
 DIFFERENT FROM THOSE ALREADY TESTED &
 PUBLISHED BY SIMPSON. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.