2004-01-15 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-ARCHITECT TO COMPLY WITH ALL REQUIRE- |
| MENTS OF CHAPTER 481 FLORIDA STATUTES |
| WHEN SUBMITTING DWGS FOR PUBLIC RECORD |
| 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| PRODUCT APPROVAL FOR: ALL DOORS/WINDOW |
| TYPE, GLASS BLOCK MULLIONS, ROOF TILE |
| AND STRUCTURAL CONNECTORS. |
| 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR |
| FIRE RATED GLASS BLOCK ASSEMBLY AND |
| REVISE DETAIL TO MATCH AL COMPONENTS |
| ON SUCH ASSEMBLY. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| DON'T MATCH. CHECK FASTENER SIZE. |
| 6-A)UPDATE TRUSS ANCHOR SCHEDULE AND ALL |
| DETAILS THAT ARE AFFECTED BY SECTION |
| 1609.4.3 FBC REGARDING STEEL STRESS. |
| NEED ENGINEERING CALCS FOR DIFFERENT |
| VALUES AND FASTENERS OTHER THAN THOSE |
| PUBLISHED ON REVISED CATALOGUES. |
| B)SPECIFY SIZE OF USP RT STRAPS. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 7-DESIGNER OF RECORD TO SPECIFY ROOF |
| TILE FASTENERS. SEC. 104.2.1.1 CITY |
| AMENDMENTS TO FBC 2001. |
| 8-REVISE WINDOW BUCK DETAIL. SEE SEC. |
| 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| INSTALLATION. |
| 9-A)DESIGN PRESSURES FOR EXTERIOR OPG'S |
| DON'T MATCH TABLES 1606.2B & 1606.2E |
| FBC 2001 ACCORDING TO SIZE/LOCATION. |
| PROVIDE CALCULATIONS FOR PRESSURES |
| THAT AREN'T CLOSE TO ABOVE TABLES. SEC |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| B)PROVIDE CALCULATIONS TO SHOW SIMPSON |
| EG-7 CONNECTOR COMPLIANCE WITH SECTION |
| 1609.4.3 FBC 2001 SINCE FASTENERS ARE |
| DIFFERENT FROM THOSE ALREADY TESTED & |
| PUBLISHED BY SIMPSON. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT 805-6712. |