2004-01-23 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-REVISE ADDRESS ON NOTICE OF COMMENCE- |
| MENT. LOT 10 IS 2254 EGRET COVE DR. |
| NOT 2454 EGRET COVE DR. |
| 2-ARCHITECT IS MISSING SOMEINFORMATION |
| ON SOME DRAWINGS AS REQ'D BY CHAPTER |
| 481 FL ST. NEED NAME AND DATE. |
| 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| DON'T MATCH. CHECK SIZE OF FASTENER. |
| 4-TRUSS ANCHOR SCHEDULE: PROVIDE CALCS |
| FOR FASTENERS TYPE/NUMBER DIFFERENT |
| THAN THOSE TESTED AND PUBLISHED BY |
| USP TO SATISFY SEC. 1609.4.3 FBC 2001. |
| 5-SPECIFY ROOF TILE FASTENERS AS REQ'D |
| BY SEC. 104.2.1.1 CITY AMENDMENTS TO |
| FBC 2001 AND SEC. 1606.3 FBC 2001. |
| 6-REVISE WINDOW BUCK DETAIL. SEE SECTION |
| 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| INSTALLATION. |
| 7-SHEET #3: A)REVISE/CLARIFY EXTERIOR |
| OPENINGS DESIGN PRESSURES ACCORDING TO |
| SIZE AND LOCATION IN WALL. SECTION |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| B)PROVIDE CALCS FOR FASTENERS USED FOR |
| EG7 CONNECTOR, SINCE THEY DIFFER FROM |
| THOSE TESTED AND PUBLISHED BY SIMPSON |
| TO SATISFY SEC. 1609.4.3 FBC 2001. |