2004-01-15 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO COMPLY WITH ALL REQUIRE-
 MENTS OF CHAPTER 481 FLORIDA STATUTES.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: ALL WINDOW/DOOR
 TYPES, ROOF TILE, MULLIONS, GLASS
 BLOCK AND ALL STRUCTURAL COMPONENTS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL TO SHOW ALL COMPONENTS
 REQUIRED ON THE LISTED ASSEMBLY.
 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK FASTENER SIZE.
 6-TRUSS ANCHOR SCHEDULE: A)UPDATE TRUSS
 ANCHOR SCHEDULE TO COMPLY WITH SECTION
 1609.4.3 FBC REGARDING STEEL STRESS.
 PROVIDE ENGINEERING CALCS FOR VALUES
 OTHER THAN THOSE PUBLISHED. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)SPECIFY SIZE OF USP RT STRAPS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-DESIGN PRESSURES AT EXTERIOR OPENINGS
 DIFFER THOSE SHOWN ON TABLES 1606.2B
 AND 1606.2E FBC 2001 ACCORDING TO SIZE
 & LOCATION. PROVIDE ENGINEERING CALCS
 FOR DIFFERENT DESIGN PRESSURES. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 10-PROVIDE ENGINEERING CALCS FOR SIMPSON
 EG7 CONNECTOR SHOWING COMPLIANCE WITH
 SEC. 1609.4.3 FBC 2001. FASTENERS ARE
 DIFFERENT FROM THOSE PUBLISHED ON
 CATALOGUE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.