2004-01-22 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-SOME DRAWINGS ARE MISSING INFORMATION |
| REQUIRED BY ARCHITECT TO BE INCLUDED |
| IN ALL PLAN AS REQ'D BY CHAPTER 471 |
| FLORIDA STATUTES. |
| 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| INFORMATION FOR ALL DOORS, WINDOWS, |
| GLASS BLOCK, ROOF TILE, MULLIONS AND |
| STRUCTURAL CONNECTORS PRIOR TO INSTA- |
| LLATION. |
| 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| DON'T MATCH. CHECK FASTENER SIZE. |
| 4-TRUSS ANCHOR SCHEDULE: PROVIDE CALCS |
| FOR TYPE/NUMBER OF FASTENERS OTHER |
| THAN THOSE TESTED AND PUBLISHED BY USP |
| TO COMPLY WITH SEC. 1609.4.3 FBC 2001 |
| REGARDING STEEL STRESS INCREASE. |
| 5-DESIGNER OF RECORD TO SPECIFY ROOF |
| TILE FASTENERS AS REQ'D BY SECTION |
| 104.2.1.1 CITY AMENDMENTS TO FBC 2001. |
| 6-REVISE WINDOW BUCK DETAIL. SEE SECTION |
| 1707.4.42 FBC 2001 FOR PROPER BUCK |
| INSTALLATION. |
| 7-SHEET #3: A)REVISE DESIGN PRESSURES. |
| SEE TABLES 1606.2B AND 1606.2E FOR |
| DESIGN PRESSURES ACCORDING TO SIZE AND |
| LOCATION. |
| B)PROVIDE ENGINEERING CALCULATIONS FOR |
| SIMPSON EG7 FASTENERS, SINCE THEY ARE |
| DIFFERENT THAN THOSE TESTED AND |
| PUBLISHED BY USP TO COMPLY WITH SEC. |
| 1609.4.3 FBC 2001 REGARDING THE STEEL |
| STRESS INCREASE. |