2004-01-14 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO COMPLY WITH ALL REQUIRE-
 MENTS OF CHAPTER 481 FLORIDA STATUTES
 WHEN SUBMITTING DWGS FOR PUBLIC RECORD
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR: SLIDER WINDOWS,
 GLASS BLOCK, ROOF TILE, SINGLE HUNG
 WINDOWS, ENTRY DOOR WITH SIDELITE,
 FIXED WINDOWS, SLIDING GLASS DOORS,
 TRUSS CONNECTORS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL TO MATCH ALL COMPONENTS
 SPECIFIED ON THE LISTING. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL DOESN'T MATCH NOTE
 ON DWG #2. SEE FASTENER SIZE. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 6-A)UPDATE TRUSS ANCHOR SCHEDULE AND
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC REGARDING STEEL STRESS.
 B)SPECIFY SIZE OF USP RT STRAP. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER AS REQUIRED BY SECTION
 104.2.1.1 CITY AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-SHEET #3B: A)CLARIFY DESIGN PRESSURES
 CALCULATED FO EXTERIOR OPENINGS. THEY
 DEVIATE FROM TABLES 1606.2B & 1606.2E
 ACCORDING TO SIZE/LOCATION. PROVIDE
 CALCULATIONS FOR DESIGN PRESSURES THAT
 ARE DIFFERENT FROM ABOVE MENTIONED
 TABLES. SEC. 104.2.1.2 CITY AMENDMENTS
 TO FBC 2001.
 B)CONNECTOR SIMPSON EG7 SHOWS DIFFERENT
 FASTENERS AS PUBLISHED ON CATALOGUE.
 PROVIDE ENGINEERING SHOWING HOW THIS
 CONNECTOR COMPLIES WITH SEC. 1609.4.3
 FBC 2001 WHICH DOESN'T ALLOW THE STEEL
 STRESS TO BE INCREASED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.