2004-01-09 00:00:00BUILDING REVIEW CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-STORM SHUTTERS: A)REVISE KEY PLAN AND
 INSTALLATION SCHEDULE. NEED EMERGENCY
 EGRESS THAT COMPLIES WITH SECTION
 1005.4.5 FBC 2001. MAKE SURE KEY PLAN
 MATCHES FLOOR PLAN SUBMITTED.
 B)CLEARLY INDICATE ANCHOR TYPE & SPACING
 TO BE USED ACCORDING TO EDGE DISTANCE,
 PANEL SPAN, CONNECTION TYPE, DESIGN
 PRESSURES & STRUCTURE TO BE ATTACHED
 TO (MASONRY OR CONCRETE).
 3-PROVIDE FLORIDA PRODUCT APPROVAL FOR:
 A)HORIZONTAL SLIDER WINDOW: NEED THE
 APPROVED DRAWINGS.
 B)GLASS BLOCK.
 C)ROOF TILE(FBC APPROVAL IS PENDING)
 D)SINGLE HUNG WINDOWS.
 E)ENTRY DOOR WITH SIDELITE ASSEMBLY.
 F)SLIDING GLASS DOORS.
 G)WINDOW MULLIONS.
 H)TRUSS CONNECTORS.
  
 4-ARCHITECT TO HAVE ALL HIS INFORMATION
 ON TITLE BLOCK AS REQUIRED BY CHAAPTER
 481 FLORIDA STATUTES. SEE FAC SECTION
 61G1-16004.
 **THIS COMMENT HAS BEEN ADDRESSED ON
 PREVIOUS REVIEWS.
 5-1 HR FIRE RATED GLASS BLOCK ASSEMBLY
 NEED SPECIFIC UL LISTED ASSEMBLY AND
 REVISE DETAIL TO MATCH SUCH ASSEMBLY.
 SPECIFY ALL COMPONENTS REQUIRED TO
 MEET THE ONE HR FIRE RATED ASSEMBLY.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 6-CLARIFY GARAGE DOOR BUCK SPECS. DETAIL
 E/4 AND NOTES ON DWG #2 DON'T MATCH.
 CHECK SIZE OF FASTENER. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 7-REVISE/UPDATE TRUSS ANCHOR SCHEDULE &
 ALL DETAILS THAT ARE AFFECTED BY SEC.
 1609.4.3 FBC 2001.
 B)SPECIFY USP RT SIZES TO VERIFY VALUE
 SPECIFIED ON CATALOGUE.
 8-ENGINEER TO SPECIFY ROOF TILE FASTENER
 AS REQ'D BY SEC. 104.2.1.1 OF CITY
 AMENDMENTS TO FBC 2001.
 9-REVISE WINDOW BUCK DETAIL. SEE SECTION
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 10-SHEET #7: A)CLARIFY WHERE IS USP
 EHUH 28-3 TAKEN FROM?. UNABLE TO FIND
 IN 2003 CATALOGUE. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 B)MISSING SPECIFICATIONS FOR CONNECTOR
 AT ONE END OF GIRDER TRUSS AT REAR
 PORCH. SEC. 104.2.1.2 CITY AMENDMENTS.
 C)REAR ELEVATION: CLARIFY CALCULATED
 DESIGN PRESSURES. WHY SAME PRESSURES
 FOR DIFFERENT SIZE/LOCATION OF OPG'S?
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT (561)805-6712.