2004-01-14 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| PRODUCT APPROVAL FOR: SLIDER WINDOWS, |
| GLASS BLOCK, ROOF TILE, SINGLE HUNG |
| WINDOWS, ENTRY DOOR WITH SIDELITE, |
| SLIDING GLASS DOORS, WINDOW MULLIONS |
| AND TRUSS CONNECTORS. |
| 3-ARCHITECT TO PROVIDE AND FOLLOW ALL |
| REQUIREMENTS OF CHAPTER 481 FLORIDA |
| STATUTES WHEN SUBMITTING DRAWINGS FOR |
| PUBLIC RECORDS. |
| 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR |
| FIRE RATED GLASS BLOCK ASSEMBLY AND |
| REVISE DETAIL TO MATCH ALL COMPONENTS |
| LISTED ON THE LISTED ASSEMBLY. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 5-GARAGE BUCK DETAIL E/4 DON'T MATCH |
| NOTES ON DWG #2. SEE FASTENER SIZE. |
| 6-REVISE/UPDATE TRUSS ANCHOR SCHEDULE & |
| ALL DETAILS THAT ARE AFFECTED BY SEC. |
| 1609.4.3 FBC REGARDING STEEL STRESS. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| B)SPECIFY SIZE OF USP RT STRAPS. SEC. |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| 7-DESIGNER OF RECORD TO SPECIFY ROOF |
| TILE FASTENER. SEC. 104.2.1.1 CITY |
| AMENDMENTS TO FBC 2001. |
| 8-REVISE WINDOW BUCK DETAIL. SEE SEC. |
| 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| INSTALLATION. |
| 9-SHEET #7: A)WHERE IS USP EHUH 28-3 |
| CONNECTOR TAKEN FROM?. UNABLE TO FIND |
| IN 2003 USP CATALOGUE. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| B)MISSING ONE CONNECTOR AT GIRDER TRUSS |
| AT REAR PORCH. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| C)DESIGN PRESSURES FOR OPENINGS WITH |
| DIFFERENT SIZE ARE THE SAME. WHY?. SEC |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| D)WINDOWS SHOWN ON EXTERIOR ELEVATION |
| DON'T MATCH WINDOW SCHEDULE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT 805-6712. |