2004-01-26 00:00:00 | BUILDING REVIEW APPROVED WITH PROVISO: |
| 1-SOME DRAWINGS NEED TO HAVE ALL INFO. |
| REQUIRED BY THE ARCHITECT AS REQ'D |
| BY CHAPTER 481 FLORIDA STATUTES. |
| 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| PRODUCT APPROVAL FOR DOORS, WINDOWS, |
| ROOF TILE, GLASS BLOCK, MULLIONS AND |
| STRUCTURAL CONNECTORS. |
| 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| DON'T MATCH. CHECK FASTENER SIZE. |
| 4-TRUSS ANCHOR SCHEDULE: PROVIDE CALCS |
| FOR TYPE/NUMBER OF FASTENERS WHEN THEY |
| ARE DIFFERENT THAN THOSE TESTED AND |
| PUBLISHED ON CATALOGUE TO COMPLY WITH |
| SEC. 1609.4.3 FBC 2001. |
| 5-DESIGNER OF RECORD TO SPECIFY ROOF |
| TILE FASTENERS. SEC. 104.2.1.1 CITY |
| AMENDMENTS TO FBC 2001. |
| 6-REVISE WINDOW BUCK DETAIL. SEE SEC. |
| 1707.4.42 FBC 2001 FOR PROPER BUCK |
| INSTALLATION. |
| 7-SHEET #3: A)REVISE/CLARIFY EXTERIOR |
| OPENINGS DESIGN PRESSURES ACCORDING |
| TO SIZE AND LOCATION. SEC. 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| B)PROVIDE ENGINEERING CALCS FOR SYMPSON |
| EG7 FASTENERS, SINCE THEY ARE DIFFEENT |
| FROM THOSE TESTED AND PUBLISHED TO |
| COMPLY WITH SEC. 1609.4.3 FBC 2001. |