Plan Review Notes
Plan Review Notes For Permit 03121446
Permit Number 03121446
Review Stop B
Sequence Number 2
Notes
Date Text
2004-01-26 00:00:00BUILDING REVIEW APPROVED WITH PROVISO:
 1-SOME DRAWINGS NEED TO HAVE ALL INFO.
 REQUIRED BY THE ARCHITECT AS REQ'D
 BY CHAPTER 481 FLORIDA STATUTES.
 2-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR DOORS, WINDOWS,
 ROOF TILE, GLASS BLOCK, MULLIONS AND
 STRUCTURAL CONNECTORS.
 3-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK FASTENER SIZE.
 4-TRUSS ANCHOR SCHEDULE: PROVIDE CALCS
 FOR TYPE/NUMBER OF FASTENERS WHEN THEY
 ARE DIFFERENT THAN THOSE TESTED AND
 PUBLISHED ON CATALOGUE TO COMPLY WITH
 SEC. 1609.4.3 FBC 2001.
 5-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 6-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.42 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 7-SHEET #3: A)REVISE/CLARIFY EXTERIOR
 OPENINGS DESIGN PRESSURES ACCORDING
 TO SIZE AND LOCATION. SEC. 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 B)PROVIDE ENGINEERING CALCS FOR SYMPSON
 EG7 FASTENERS, SINCE THEY ARE DIFFEENT
 FROM THOSE TESTED AND PUBLISHED TO
 COMPLY WITH SEC. 1609.4.3 FBC 2001.