Plan Review Notes
Plan Review Notes For Permit 03121446
Permit Number 03121446
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-14 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO COMPLY WITH ALL REQUIRE-
 MENTS OF CHAPTER 481 WHEN SUBMITTING
 DRAWINGS FOR PUBLIC RECORD.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR EXTERIOR DOOR AND
 WINDOWS, ROOF TILE AND TRUSS ANCHORS.
 4-PROVIDE SPECIFIC UL LISTING FOR GLASS
 BLOCK RATED 1HR RATED ASSEMBLY AND
 REVISE DETAIL TO MATCH LISTED ASSEMBLY
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK FASTENER SIZE.
 6-TRUSS ANCHOR SCHEDULE: SPECIFY SIZE OF
 USP RT STRAP USED. SEC. 104.2.1.2 CITY
 AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENERS. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-A)REVISE DESIGN PRESSURES FOR EXTERIOR
 OPENINGS. SEE TABLES 1606.2B AND
 1606.2E ACCORDING TO SIZE & LOCATION.
 PROVIDE CALCULATIONS FOR DESIGN PRESSU
 RES THAT DIFFER FROM ABOVE TABLES. SEC
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 B)SIMPSON EG7 CONNECTOR HAS DIFFERENT
 FASTENERS THAN SHOWN ON CATALOGUE.
 PROVIDE ENGINEERING CALCS SHOWING
 COMPLIANCE WITH SEC. 1609.4.3 FBC 2001
 REGARDING STEEL STRESS INCREASE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.