2004-01-14 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-ARCHITECT TO COMPLY WITH ALL REQUIRE- |
| MENTS OF CHAPTER 481 WHEN SUBMITTING |
| DRAWINGS FOR PUBLIC RECORD. |
| 2-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC |
| PRODUCT APPROVAL FOR EXTERIOR DOOR AND |
| WINDOWS, ROOF TILE AND TRUSS ANCHORS. |
| 4-PROVIDE SPECIFIC UL LISTING FOR GLASS |
| BLOCK RATED 1HR RATED ASSEMBLY AND |
| REVISE DETAIL TO MATCH LISTED ASSEMBLY |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2 |
| DON'T MATCH. CHECK FASTENER SIZE. |
| 6-TRUSS ANCHOR SCHEDULE: SPECIFY SIZE OF |
| USP RT STRAP USED. SEC. 104.2.1.2 CITY |
| AMENDMENTS TO FBC 2001. |
| 7-DESIGNER OF RECORD TO SPECIFY ROOF |
| TILE FASTENERS. SEC. 104.2.1.1 CITY |
| AMENDMENTS TO FBC 2001. |
| 8-REVISE WINDOW BUCK DETAIL. SEE SEC. |
| 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| INSTALLATION. |
| 9-A)REVISE DESIGN PRESSURES FOR EXTERIOR |
| OPENINGS. SEE TABLES 1606.2B AND |
| 1606.2E ACCORDING TO SIZE & LOCATION. |
| PROVIDE CALCULATIONS FOR DESIGN PRESSU |
| RES THAT DIFFER FROM ABOVE TABLES. SEC |
| 104.2.1.2 CITY AMENDMENTS TO FBC 2001. |
| B)SIMPSON EG7 CONNECTOR HAS DIFFERENT |
| FASTENERS THAN SHOWN ON CATALOGUE. |
| PROVIDE ENGINEERING CALCS SHOWING |
| COMPLIANCE WITH SEC. 1609.4.3 FBC 2001 |
| REGARDING STEEL STRESS INCREASE. |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| JULIO GOMEZ AT 805-6712. |