Plan Review Notes
Plan Review Notes For Permit 03121445
Permit Number 03121445
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-15 00:00:00BUILDING REVIEW CHECKLIST:
 1-ARCHITECT TO COMPLY WITH CHAPTER 481
 FLORIDA STATUTES WHEN SUBMITTING DWGS
 FOR PUBLIC RECORDS.
 2-NEED RECORDED NOTICE OF COMMENCEMENT.
 3-PROVIDE COMPLETE FLORIDA/SITE SPECIFIC
 PRODUCT APPROVAL FOR ALL DOORS/WINDOWS
 TYPE, MULLIONS, GLASS BLOCK, ROOF TILE
 AND ALL STRUCTURAL CONNECTORS.
 4-PROVIDE SPECIFIC UL LISTING FOR ONE HR
 FIRE RATED GLASS BLOCK ASSEMBLY AND
 REVISE DETAIL ACCORDINGLY. SECTION
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 5-GARAGE BUCK DETAIL AND NOTES ON DWG #2
 DON'T MATCH. CHECK FASTENERS.
 6-UPDATE TRUSS ANCHOR SCHEDULE AND ALL
 DETAILS TO COMPLY WITH SEC. 1609.4.3
 FBC 2001.PROVIDE ENGINEERING CALCS
 FOR DIFFERENT VALUES AND FASTENERS.
 SEE REVISE CATALOGUES.
 B)SPECIFY SIZE FOR RT USP STRAPS. SEC.
 104.2.1.2 CITY AMENDMENTS TO FBC 2001.
 7-DESIGNER OF RECORD TO SPECIFY ROOF
 TILE FASTENER. SEC. 104.2.1.1 CITY
 AMENDMENTS TO FBC 2001.
 8-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 9-REVISE DESIGN PRESSURES FOR EXTERIOR
 OPENINGS. SEE TABLES 1606.2B AND
 1606.2E FOR PRESSURES ACCORDING TO
 SIZE AND LOCATION. PROVIDE ENGINEERING
 CALCS FOR DIFFERENT VALUES.
 10-PROVIDE ENGINEERING CALCS FOR SIMPSON
 EG-7 CONNECTOR SHOWING COMPLIANCE WITH
 SEC. 1609.4.3 FBC REGARDING THE STEEL
 STRESS SINCE FASTENERS AREN'T THE SAME
 AS TESTED AND PUBLISHED BY SIMPSON.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.