Plan Review Notes
Plan Review Notes For Permit 03121436
Permit Number 03121436
Review Stop E
Sequence Number 3
Notes
Date Text
2005-06-28 00:00:00********* UNSAT *********
  
 1)NOTE: PLEASE SEE PLANS MUST CONTAIN
 THE PRINTED NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR PLANS AND /OR
 DESIGN.
 FBC 104.2.1
  
 2)NOTE: PLEASE SEE ONLY ONE SM APPL
 CIRCUIT IS INDICATED IN LOAD
 CALCULATIONS AND "KITCHEN OUTLETS" ARE
 SHOWN ON PANEL SCHEDULE. PLEASE SEE
 210.52B1, 220.16,210.11C1, A MIN OF TWO
 "SMALL APPLIANCE" CIRCUITS ARE REQUIRED
 ON PANEL SCHEDULE AND LOAD CALCULATIONS.
  
 3)NOTE: PLEASE SEE RECEPT/CONN FOR
 JACUZZI TUB IS BE SHOWN AS GFI/ GFI
 PROTECTED. 680.71
  
 4)NOTE: PLEASE SEE MISSING GROUNDING
 ELECTRODE CONDUCTOR PER 250.50, 250.66
 #2 MIN.
  
 5)NOTE: PLEASE SEE MISSING RECEPT IN
 LEISURE RM. 210.52
  
 6)NOTE: PLEASE INDICATE LOADS FOR
 PANELS.
 PLEASE SEE ALL CONTINUOUS LOADS ARE TO
 BE SHOWN @125%.(POOL PUMP, POOL HEAT
 PUMP).
 215.5,220.31,680.9 ETC.215.3,230.42, 100
 ETC.
  
 7)NOTE: PLEASE SEE PANEL "C" IS MISSING
 FROM PLANS? PLEASE ALSO SEEE PANEL "C"
 IS SHOWN ASMBP? THIS IS ONLY A NOTE
 ABOUT THE MB INDICATED. IF SHOWN AS MCB
 THEN A MCB WILL BE REQUIRED.
 PLEASE SEE "TAN" SHOWN FOR COLOR OF
 CONDUCTORS??
  
 PLEASE SUBMIT THE ABOVE INFORMAITON FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]