2003-12-31 00:00:00 | *********** UNSAT ************* |
| |
| |
| *** NOTE*** UNABLE TO DUE COMPLETE |
| REVIEW AT THIS TIME DUE TO PLANS MISSING |
| RISER DIAGRAM FOR SERVICE. |
| |
| |
| 1)NOTE: PLEASE SUBMIT COMPLETE RISER |
| DIAGRAM. 215.5,250.50,110.9, 310.15B6 |
| 250.66 ETC |
| |
| 2)NOTE: PLEASE CLARIFY MASTER BATH NOT |
| SHOWN ON PANEL SCHEDULE? OTHER BATHS |
| SHOWN AND PER 210.52D,210.11C3 OTHER |
| BATHS MAY NOT BE ON EITHER OF THESE. |
| |
| 3)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| -ED. PER 210.8A6 |
| |
| 4)NOTE: PLEASE SEE 210.52C1 FOR RECEPT |
| SPACING ALONG KITCHEN COUNTERSPACE. |
| MISSING A FEW. |
| |
| 5)NOTE: PLEASE SHOW /NOTE ALL OUTSIDE/ |
| GARAGE RECEPTS AS GFI. 210.8 |
| |
| 6)NOTE: PLEASE SEE MISSING RECEPT FOR |
| LIVING RM PER 210.52/ 2' WALL. |
| |
| 7)NOTE: PLEASE SEE THAT NOTE ON PLAN |
| MENTIONS SD TO BE 3' FROM RETURN. |
| PLEASE SEE NFPA-72, STATES TO BE 3' FROM |
| SUPPLY GRILLES. NFPA DOES NOT STATE R/A |
| TYP PER MANF SPECS AND CITY OF WPB SD'S |
| ARE TO BE 5' FROM RETURN AIR. |
| |
| 8)NOTE: PLEASE SEE THAT PLANS ONLY |
| SHOW ONEA/C CONDENSER UNIT? |
| PLEASE SHOW ADDITIONAL UNIT AS SHOWN |
| ON PANEL SCHEDULE. |
| PLEASE ALSO SHOW/CLARIFY LOCATION OF |
| AHU #2? ALSO 210.70/210.63 LOCATIONS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |