2003-12-31 00:00:00*********** UNSAT *************
  
  
 *** NOTE*** UNABLE TO DUE COMPLETE
 REVIEW AT THIS TIME DUE TO PLANS MISSING
 RISER DIAGRAM FOR SERVICE.
  
  
 1)NOTE: PLEASE SUBMIT COMPLETE RISER
 DIAGRAM. 215.5,250.50,110.9, 310.15B6
 250.66 ETC
  
 2)NOTE: PLEASE CLARIFY MASTER BATH NOT
 SHOWN ON PANEL SCHEDULE? OTHER BATHS
 SHOWN AND PER 210.52D,210.11C3 OTHER
 BATHS MAY NOT BE ON EITHER OF THESE.
  
 3)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. PER 210.8A6
  
 4)NOTE: PLEASE SEE 210.52C1 FOR RECEPT
 SPACING ALONG KITCHEN COUNTERSPACE.
 MISSING A FEW.
  
 5)NOTE: PLEASE SHOW /NOTE ALL OUTSIDE/
 GARAGE RECEPTS AS GFI. 210.8
  
 6)NOTE: PLEASE SEE MISSING RECEPT FOR
 LIVING RM PER 210.52/ 2' WALL.
  
 7)NOTE: PLEASE SEE THAT NOTE ON PLAN
 MENTIONS SD TO BE 3' FROM RETURN.
 PLEASE SEE NFPA-72, STATES TO BE 3' FROM
 SUPPLY GRILLES. NFPA DOES NOT STATE R/A
 TYP PER MANF SPECS AND CITY OF WPB SD'S
 ARE TO BE 5' FROM RETURN AIR.
  
 8)NOTE: PLEASE SEE THAT PLANS ONLY
 SHOW ONEA/C CONDENSER UNIT?
 PLEASE SHOW ADDITIONAL UNIT AS SHOWN
 ON PANEL SCHEDULE.
 PLEASE ALSO SHOW/CLARIFY LOCATION OF
 AHU #2? ALSO 210.70/210.63 LOCATIONS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  