2004-02-11 00:00:00BUILDING REVIEW CHECKLIST:
 1-PROVIDE IMPACT FEES PAID RECEIPT.
 2-SURVEY SAYS FLOOD ZONE A8. FLOOD ZONE
 WAS CHANGED TO B PER LETTER OF MAP
 REVISION DATED DEC 3 1985. REVISE INFO
 ON SURVEY AS REQUIRED.
 3-AS OF OCT. 1ST 2003 NEED TO PROVIDE
 FLORIDA OR LOCAL PRODUCT APPROVAL FOR
 ALL TYPES OF DOORS, WINDOWS, MULLIONS
 (AS SHOWN ON PLANS), ROOF TILE AND ALL
 STRUCTURAL CONNECTORS AS REQUIRED BY
 RULE 9B-72.
 4-NEED RECORDED NOTICE OF COMMENCEMENT.
 5-DRAWING #3 IS MISSING ENGINEER'S LOGO
 AND SEAL, SIGNATURE AND DATE.
 6-SPECIFY ROOF TILE FASTENERS. SEE SEC.
 1606.3 FBC 2001 AND SECTION 104.2.1.1
 CITY AMENDMENTS TO FBC 2001.
 7-PROVIDE COMPLETE SECTION/DETAIL THRU
 MASONRY COLUMNS @ ENTRY AND REAR PORCH
 SHOWING FOOTING LOCATION IN RELATION
 TO FINISH GRADE. ALSO, NEED TO SHOW
 COMPLETE SPECS FOR VERTICAL REINFORCE-
 MENT. PROVIDE CALCULATIONS TO SHOW HOW
 THESE COLUMNS (FRONT AND REAR WILL
 PROVIDE SUPPORT FOR UPLIFT LOADS).
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 8-SPECIFY SIZE OF ATTIC ACCESS. SEE SEC.
 2309.6 FBC 2001.
 9-PROVIDE COMPLETE DETAIL AND SPECS FOR
 HANGING OF AHU. SPECIFY ALL FASTENERS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 10-SHEET #5B: A)SPECIFY TRUSS CONNECTORS
 FOR ALL TRUSSES.
 B)PROVIDE DETAILS FOR INSTALLATION OF #
 OF ANCHORS AT UNION OF TRUSSES TO COLS
 AS SPECIFIED ON TRUSS ANCHOR SCHEDULE.
 SEE ROOF FRAMING PLAN FOR COMMENTS.
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 11-REVISE DETAIL 28/4S2. SEE ZONE 3 ON
 FIGURE 1606.2(C) FBC 2001.
 12-PROVIDE DETAIL/SPECS FOR INSTALLATION
 OF CEILING AT ENTRY AND REAR PORCH.
 SEE ASTM C-926 & ASTM C-1063. SPECIFY
 STUCCO THICKNESS AND FASTENER SIZE AND
 SPACING. SEC. 2504.2 FBC 2001.
 13-SHOW ONLY DETAILS THAT APPLY TO THIS
 PROJECT.
 14-REVISE WINDOW BUCK DETAIL. SEE SEC.
 1707.4.4.2 FBC 2001 FOR PROPER BUCK
 INSTALLATION.
 15-GARAGE BUCK DETAIL 3/4S1 AND DETAIL
 3/4S4 DON'T MATCH. CHECK SIZE AND MIN.
 NUMBER OF ANCHORS. ALSO,SPECIFY ANCHOR
 SPACING AT THE END OF BUCK AND SPECIFY
 SIZE OF WASHERS. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.
 16-DWG #4S4: CLARIFY BUTT GLAZING NOTE:
 IS THERE ANY BUTT GLAZING IN MORNING
 AREA OR THERE ARE FIXED WINDOWS WITH
 STOREFRONT SYSTEM? EITHER WAY NEED
 PRODUCT APPROVAL. SEE SEC. 2406.2 FBC.
 17-PROVIDE AREA TABULATIONS INCLUDING
 A/C AREAS, PORCHES, GARAGE ETC.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ AT 805-6712.