2004-02-11 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1-PROVIDE IMPACT FEES PAID RECEIPT. |
| 2-SURVEY SAYS FLOOD ZONE A8. FLOOD ZONE |
| WAS CHANGED TO B PER LETTER OF MAP |
| REVISION DATED DEC 3 1985. REVISE INFO |
| ON SURVEY AS REQUIRED. |
| 3-AS OF OCT. 1ST 2003 NEED TO PROVIDE |
| FLORIDA OR LOCAL PRODUCT APPROVAL FOR |
| ALL TYPES OF DOORS, WINDOWS, MULLIONS |
| (AS SHOWN ON PLANS), ROOF TILE AND ALL |
| STRUCTURAL CONNECTORS AS REQUIRED BY |
| RULE 9B-72. |
| 4-NEED RECORDED NOTICE OF COMMENCEMENT. |
| 5-DRAWING #3 IS MISSING ENGINEER'S LOGO |
| AND SEAL, SIGNATURE AND DATE. |
| 6-SPECIFY ROOF TILE FASTENERS. SEE SEC. |
| 1606.3 FBC 2001 AND SECTION 104.2.1.1 |
| CITY AMENDMENTS TO FBC 2001. |
| 7-PROVIDE COMPLETE SECTION/DETAIL THRU |
| MASONRY COLUMNS @ ENTRY AND REAR PORCH |
| SHOWING FOOTING LOCATION IN RELATION |
| TO FINISH GRADE. ALSO, NEED TO SHOW |
| COMPLETE SPECS FOR VERTICAL REINFORCE- |
| MENT. PROVIDE CALCULATIONS TO SHOW HOW |
| THESE COLUMNS (FRONT AND REAR WILL |
| PROVIDE SUPPORT FOR UPLIFT LOADS). |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 8-SPECIFY SIZE OF ATTIC ACCESS. SEE SEC. |
| 2309.6 FBC 2001. |
| 9-PROVIDE COMPLETE DETAIL AND SPECS FOR |
| HANGING OF AHU. SPECIFY ALL FASTENERS. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 10-SHEET #5B: A)SPECIFY TRUSS CONNECTORS |
| FOR ALL TRUSSES. |
| B)PROVIDE DETAILS FOR INSTALLATION OF # |
| OF ANCHORS AT UNION OF TRUSSES TO COLS |
| AS SPECIFIED ON TRUSS ANCHOR SCHEDULE. |
| SEE ROOF FRAMING PLAN FOR COMMENTS. |
| SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| 11-REVISE DETAIL 28/4S2. SEE ZONE 3 ON |
| FIGURE 1606.2(C) FBC 2001. |
| 12-PROVIDE DETAIL/SPECS FOR INSTALLATION |
| OF CEILING AT ENTRY AND REAR PORCH. |
| SEE ASTM C-926 & ASTM C-1063. SPECIFY |
| STUCCO THICKNESS AND FASTENER SIZE AND |
| SPACING. SEC. 2504.2 FBC 2001. |
| 13-SHOW ONLY DETAILS THAT APPLY TO THIS |
| PROJECT. |
| 14-REVISE WINDOW BUCK DETAIL. SEE SEC. |
| 1707.4.4.2 FBC 2001 FOR PROPER BUCK |
| INSTALLATION. |
| 15-GARAGE BUCK DETAIL 3/4S1 AND DETAIL |
| 3/4S4 DON'T MATCH. CHECK SIZE AND MIN. |
| NUMBER OF ANCHORS. ALSO,SPECIFY ANCHOR |
| SPACING AT THE END OF BUCK AND SPECIFY |
| SIZE OF WASHERS. SECTION 104.2.1.2 |
| CITY AMENDMENTS TO FBC 2001. |
| 16-DWG #4S4: CLARIFY BUTT GLAZING NOTE: |
| IS THERE ANY BUTT GLAZING IN MORNING |
| AREA OR THERE ARE FIXED WINDOWS WITH |
| STOREFRONT SYSTEM? EITHER WAY NEED |
| PRODUCT APPROVAL. SEE SEC. 2406.2 FBC. |
| 17-PROVIDE AREA TABULATIONS INCLUDING |
| A/C AREAS, PORCHES, GARAGE ETC. |
| |
| |