Plan Review Notes For Permit 03121424 |
Permit Number |
03121424 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-01-07 00:00:00 | DENIED: | | 1.FIRE DAMPER IS NOT INDICATED ON THE | | EXISTING HIGH PRESSURE DUCT PENETRATING | | THE WALL IN OFFICE #100.PLEASE VERIFY | | EXISTING OR NEW FIRE DAMPER AS REQUIRED | | PER 2001 FBC(M) 607.1.2 & 607.6. | | | | 2.RETURN AIR GRILLES (NEW OR EXISTING) | | NOT SHOWN IN OFFICE AREAS. | | | | 3.PLEASE NOTE, NO COMBUSTIBLES ALLOWED | | ABOVE THE CEILING IN THE RETURN AIR | | PLENUM.2001 FBC(M) 602.2.1. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|