2004-02-09 00:00:00 | UNSAT |
| ~~~~~ |
| ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING |
| INSTALL-ED. MAINS/BRKRS AND PANELS ARE |
| ALL TO BERATED FOR THE AVAILABLE FAULT |
| CURRENT. |
| PER 110.9/215.5 |
| |
| 2} PLEASE SUBMIT PANEL SCHEDULES FOR ALL |
| PANELS SO THAT CODE COMPLIANCE OF |
| CIRCUITS CAN BE DETERMINED. |
| |
| 3} PLEASE SHOW PANEL "A" LOCATION ON |
| PLAN. |
| |
| 4} PLEASE SEE RECEPTS SERVING |
| KITCHEN COUNTERSPACE TO MEET 210.52C- |
| SEC'S 1,2,3,4 AND 5.COUNTERTOP SPACING |
| IS INCORRECT. |
| |
| 5} THE BATHROOM OFF THE KITCHEN IS |
| REQUIRED TO HAVE A GFI RECEPTACLE PER |
| 210.52(D) & COMLPY WITH 210.11(C)(3). |
| |
| 6} PLEASE LIST THE REQ'D ARC |
| FAULT PROTECTED CURCUIT(S) ON PANEL |
| SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| IN BEDROOMS ARE TO BE PROTECTED , |
| INCLUDING, LTS, RECEPTS, SD'S ETC. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |
| [email protected] |
| FAX/:561/659-8026 |
| |
| |
| |
| |
| |
| 2)NOTE: PLEASE SEE BLDG PLAN REVIEW |
| NOTES. PLEASE CORRELATE PLANS/PAPERWORK |
| FOR COTTAGES. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |