Plan Review Notes For Permit 03121414 |
Permit Number |
03121414 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-01-16 00:00:00 | 1. DIFFERENT ENGINEERS USED FROM FIRST | | PLAN TO REVISED PLAN.HAVE FIRST | | ENGINNER SIGN OFF PROJECT TO NEW | | ENGINEER. | | 2.SHOW NEW STAIR FRAMING DETAIL. | | 3.SHOW INTERIOR BEARING WALL FRAMING | | DETAILS. | | 4.SUBMIT PRODUCT APPROVALS FOR EXTERIOR | | DOORS,WINDOWS, AND IMPACT PROTECTION. | | 5. SLEEPING ROOMS SHALL COMPLY WITH SEC. | | 1005.0 FBC EMERGENCY EGRESS | | REQUIREMENTS. | | 6.GLASS SHALL BE IN ACCORDANCE WITH | | SECTION FBC 2405.2.1 HAZARDOUS | | LOCATIONS. | | 7.A E-1 CLEARANCE BETWEEN WOOD AND | | GROUND FBC 2304.2.5MIN. 6" CLEARANCE | | UNLESS PRESERVATIVE-TREATED WOOD IS | | USED. | | 8.SHOW INSULATION DETAILS. | | 9.FBC. 104.6.5 BUILDING PERMIT VALUATI | | ON TOO LOW. SEE ATTACHED CODE SECTION. | | | | ART LANGE | | BUILDING PLANS EXAMINER | | 805-6672 |
|