Plan Review Notes
Plan Review Notes For Permit 03121414
Permit Number 03121414
Review Stop P
Sequence Number 1
Notes
Date Text
2004-01-10 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT E-1 SANITARY RISER DIAGRAM DOES
 NOT MEET CODE REQUIREMENTS, NOR DOES IT
 REFLECT THE FLOOR PLAN.
 A) BATH #2 SHOWS A TUB ON FLOOR PLAN.
 BUT SHOWS SHOWER ON RISER.
 B) BATH #2 TUB AND LAV NOT VENTED.
 C) MASTER BATH LAVS NOT VENTED AND NOT
 IN M/BATHROOM.
 D) MASTER BATH TUB NOT VENTED.
 2) SEE RED LINE CORRECTIONS AND EXAMPLE
 FOR MASTER BATH RISER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692