Date |
Text |
2004-01-08 00:00:00 | |
| UNSAT |
| ~~~~~ |
| ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| ON THE PLAN FOR CODE COMPLIANCE AS |
| NOTED. |
| |
| 1} THE RISER DIAGRAM SHOWS THE 200 AMP |
| PANEL AS NEW AND LISTS IT AS EXISTING |
| ON THE NOTE.IT IS AGAIN LISTED AS "NEW" |
| AT THE SITE LOCATION.PLEASE CORRELATE. |
| |
| 2} PLEASE SUBMIT AIC RATINGS FOR |
| ALL NEW SERVICE EQUIPMENT BEING |
| INSTALL-ED. MAINS/BRKRS AND PANELS ARE |
| ALL TO BERATED FOR THE AVAILABLE FAULT |
| CURRENT. |
| PER 110.9/215.5 |
| |
| 3} THE PANEL SCEDULE APPEARS TO HAVE THE |
| BREAKER AND BREAKER AMPSINCORRECT FOR |
| THEIR EQUIPMENT SERVED. |
| |
| 4} THE #6 WIRE SHOWN ON A 100 AMP |
| BREAKER (COND UNITS) DOES NOT COMPLY |
| WITH 310.16. |
| |
| 5} THE NEUTRAL FEEDING PANEL "B" IS |
| SHOWN AS #3/0,PLEASE VERIFY. |
| |
| 6} PLEASE SUBMIT PANEL SCHEDULES FOR ALL |
| PANELS SO THAT CODE COMPLIANCE OF |
| CIRCUITS AND OCP CAN BE DETERMINED. |
| |
| 7} PLEASE NOTE KITCHEN COUNTER- |
| -SPACE RECEPT SPACING SHALL MEET ART; |
| 210.52C 1,2,3,4,AND 5. |
| |
| 8} PLEASE SEE MISSING RECEPTS FOR |
| FRONT AND/OR REAR OF DWELLING. |
| 210.52E |
| |
| 9} PLEASE SEE MISSING RECEPT REQ'D |
| FOR A/C EQUIPMENT. 210.63 |
| |
| 10} PLEASE ADD THE SMOKE DETECTOR ON THE |
| FIRST FLOOR AT THE STAIR TO COMPLY WITH |
| 905.2.2 FBC AND NFPA-72 |
| |
| 11} INCREASE THE BUILDING PERMIT |
| VALUATION PER 104.6.5 CWPB AMMENDMENTS |
| TO THE FBC, ATTACHED. |
| |
| 12} ONLY ONE SET OF DRAWINGS ARE SEALED |
| BY THE ENG. ON SHEET E-1.ALSO NOTE THAT |
| SHEETS A-1 & A-2 ARE NOT SIGNED AND |
| SEALED BY THE ENGINEER OF RECORD. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW |
| 561/805-6718 |