Notes
Date Text
2004-01-08 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 ON THE PLAN FOR CODE COMPLIANCE AS
 NOTED.
  
 1} THE RISER DIAGRAM SHOWS THE 200 AMP
 PANEL AS NEW AND LISTS IT AS EXISTING
 ON THE NOTE.IT IS AGAIN LISTED AS "NEW"
 AT THE SITE LOCATION.PLEASE CORRELATE.
  
 2} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALL-ED. MAINS/BRKRS AND PANELS ARE
 ALL TO BERATED FOR THE AVAILABLE FAULT
 CURRENT.
 PER 110.9/215.5
  
 3} THE PANEL SCEDULE APPEARS TO HAVE THE
 BREAKER AND BREAKER AMPSINCORRECT FOR
 THEIR EQUIPMENT SERVED.
  
 4} THE #6 WIRE SHOWN ON A 100 AMP
 BREAKER (COND UNITS) DOES NOT COMPLY
 WITH 310.16.
  
 5} THE NEUTRAL FEEDING PANEL "B" IS
 SHOWN AS #3/0,PLEASE VERIFY.
  
 6} PLEASE SUBMIT PANEL SCHEDULES FOR ALL
 PANELS SO THAT CODE COMPLIANCE OF
 CIRCUITS AND OCP CAN BE DETERMINED.
  
 7} PLEASE NOTE KITCHEN COUNTER-
 -SPACE RECEPT SPACING SHALL MEET ART;
 210.52C 1,2,3,4,AND 5.
  
 8} PLEASE SEE MISSING RECEPTS FOR
 FRONT AND/OR REAR OF DWELLING.
 210.52E
  
 9} PLEASE SEE MISSING RECEPT REQ'D
 FOR A/C EQUIPMENT. 210.63
  
 10} PLEASE ADD THE SMOKE DETECTOR ON THE
 FIRST FLOOR AT THE STAIR TO COMPLY WITH
 905.2.2 FBC AND NFPA-72
  
 11} INCREASE THE BUILDING PERMIT
 VALUATION PER 104.6.5 CWPB AMMENDMENTS
 TO THE FBC, ATTACHED.
  
 12} ONLY ONE SET OF DRAWINGS ARE SEALED
 BY THE ENG. ON SHEET E-1.ALSO NOTE THAT
 SHEETS A-1 & A-2 ARE NOT SIGNED AND
 SEALED BY THE ENGINEER OF RECORD.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718