Plan Review Notes
Plan Review Notes For Permit 03121403
Permit Number 03121403
Review Stop B
Sequence Number 1
Notes
Date Text
2004-06-25 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT A COPY OF THE PAID RECEIPT FOR
 THE COUNTY IMPACT FEES.
  
 3) FBC* 1804.2.2AREA OF QUESTIONABLE
 SOIL.SUBMIT A GEOTECHNICAL REPORT
 TO VERIFY THE SAFE BEARING CAPACITY OF
 THE SOIL.
  
 4)ON SHEET 3 STRUCTURAL NOTE 6 SPECIFIES
 THAT REINFORCING STEEL BE LAPPED 48 BAR
 DIAMETERS. THE FILLED CELL DETAIL ON
 SHEET 1 AND COLUMN NOTE 1 ON 3 SPECIFY
 SPECIFY 30 BAR DIAMETERS. PLEASE CORRECT
  
 5) THE UPLIFTS FOR THE 2 MEMBER GIRDER
 ARE 2852PSF AND 2808PSF EXCEED THE
 UPLIFT CAPACITY OF 1215# SPECIFIED FOR
 THE HUS 26-2 IN DETAIL A ON SHEET 4.
  
 6)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SUBMIT
 PRODUCT APPROVALS FOR THE FOLLOWING:
 - STRUCTURAL MULLIONS
 - OUTSWING GLAZED DOOR (FL PRODUCT
 APPROVAL DOES NOT MATCH NOA SUBMITTED)
 - OVERHEAD GARAGE DOOR (FL# IS NOT
 CORRECT, PARTS OF REPORT SUBMITTED ARE
 ILLEGIBLE)
  
 IF YOU HAVE QUESTIONS CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714