2004-06-25 00:00:00 | DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SUBMIT A COPY OF THE PAID RECEIPT FOR |
| THE COUNTY IMPACT FEES. |
| |
| 3) FBC* 1804.2.2AREA OF QUESTIONABLE |
| SOIL.SUBMIT A GEOTECHNICAL REPORT |
| TO VERIFY THE SAFE BEARING CAPACITY OF |
| THE SOIL. |
| |
| 4)ON SHEET 3 STRUCTURAL NOTE 6 SPECIFIES |
| THAT REINFORCING STEEL BE LAPPED 48 BAR |
| DIAMETERS. THE FILLED CELL DETAIL ON |
| SHEET 1 AND COLUMN NOTE 1 ON 3 SPECIFY |
| SPECIFY 30 BAR DIAMETERS. PLEASE CORRECT |
| |
| 5) THE UPLIFTS FOR THE 2 MEMBER GIRDER |
| ARE 2852PSF AND 2808PSF EXCEED THE |
| UPLIFT CAPACITY OF 1215# SPECIFIED FOR |
| THE HUS 26-2 IN DETAIL A ON SHEET 4. |
| |
| 6)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SUBMIT |
| PRODUCT APPROVALS FOR THE FOLLOWING: |
| - STRUCTURAL MULLIONS |
| - OUTSWING GLAZED DOOR (FL PRODUCT |
| APPROVAL DOES NOT MATCH NOA SUBMITTED) |
| - OVERHEAD GARAGE DOOR (FL# IS NOT |
| CORRECT, PARTS OF REPORT SUBMITTED ARE |
| ILLEGIBLE) |
| |