Plan Review Notes For Permit 03121324 |
Permit Number |
03121324 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-02-02 00:00:00 | DENIED | | COMMENTS PERTAIN TO THE FOLLOWING PERMIT | | NUMBERS:03121251, 03121290, 03121308, | | 03121324, 03121335, 03121280 | | | | MODEL A, B, AND C | | 1.PROVIDE OUTSIDE AIR CALCULATIONS PER | | 2001 FBC(M) 402.2 OR 403.3. | | | | 2.RETURN AIR TRANSFER GRILLE FROM THE | | MASTER BEDROOM IS NOT SIZED PROPERLY. | | REFERENCE 2001 FBC(M) 601.4 EXCEPTION #2 | | AND 3. GRILLES SHALL HAVE 50 SQ INCHES | | TO 100 CFM OF SUPPLY AIR.FOR PROPER | | SIZING FOR THE RETURN TRANSFER GRILLE TO | | THE MASTER BEDROOM, ALL SUPPLY AIR TO | | THE SUITE IS TO BE INCLUDED IN THE | | CALCULATION.PLEASE REVISE. | | | | 3.AUXILIARY DRAIN PAN REQUIRED PER | | 2001 FBC(M) 307.2.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|