2004-01-29 00:00:00************** UNSAT ***************
  
 1)NOTE: PLEASE PROVIDE ADDRESS ON PLANS
 FOR JOBSITE. REQ'D ON TITLE BLOCK PER
 FAC 61G1-16.004
  
 2)NOTE: PLEASE SEE NOTES ON PLANS
 REFERENCE THE SFBC, AND THE 1999 NEC
 WHICH ARE NO LONGER IN EFFECT. PLEASE
 ADJUST NOTES AND ALL CODES REFERENCED
 ON PLANS. NEED TO CORRELATE TO THE 2002
 NEC
  
 3)NOTE: PLEASE PROVIDE CIRCUITING #'S ON
 PLANS AND PANEL SCHEDULES TO PROVIDE
 ARC FAULT PROTECTION AS REQ'D NOW UNDER
 THE 2002 NEC. AS SHOWN IS REQUIREMENTS
 UNDER 1999 NEC.
 2002 NEC WAS ADOPTED BY THE STATE JULY
 1ST ,2003.
  
 4)NOTE: PLEASE SEE REFERENCE FOR GROUND-
 ING ELECTRODE SYSTEM. SHOWN FOR 1999,
 CODE CHANGED FOR 2002.
  
 5)NOTE: PLEASE SEE NOTES FORM ANY OTHER
 REVIEWERS AS THEY MAY HAVE AN AFFECT ON
 ELECTRICAL PLANS.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 INSERT NEW SHEETS INTO TWO COMPLETE SETS
 FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT TWO COMPLETE SETS. ONLY
 ONE HERE FOR REVIEW.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  