2004-01-22 00:00:00 | THE TWO SETS OF PLANS SUBMITTED DO NOT |
| MATCH - CONTRACTOR TO INFORM WHICH PLAN |
| TO REVIEW PER TEL CALL W/MARIANA |
| REVIEW PLANS WHICH MASTER AS PER |
| MARIANA - PULLED OTHER SET OUT FOR |
| CONTRACTOR P/U |
| *****CORRECTIONS/PROVISO****** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| [email protected] |
| |
| ADDRESS ALL BUILDING CORRECTIONS AT THIS |
| TIME IF THE PLANS DO NOT PASS OTHER |
| TRADES!!!!! |
| |
| COMMENTS ALSO APPLY TO 03121290, |
| 03121308, 03121324, 03121335, 03121280 |
| |
| 1.)THE NOTICE OF COMMENCEMENT IS |
| EXPIRED FS713.13 (90 DAYS WITHOUT |
| COMMENCING WORK). |
| |
| 2.)S-1, WATERSTOP TO BE 1 1/2" CITY |
| OF WEST PALM BEACH AMENDMENTS TO THE FBC |
| 2111.1.9.CHECK ALL DETAILS. |
| |
| 3.)BOTTOM CHORD LIVE LOAD IS REQUIRED |
| TO BE 10, 30 IN ATTICS WITH STORAGE, |
| FBC TABLE 1604.1 (SHEET S8, #9). |
| |
| THE FOLLOWING COMMENTS MUST BE |
| ADDRESSED BEFORE THE PERMIT CAN BE |
| ISSUED - NO PROVISO |
| |
| 4.) SUBMIT TWO COMPLETE PACKAGES OF |
| CURRENT PRODUCT APPROVALS WITH ONLY |
| ITEMS TO BE INSTALLED ON THIS JOB. |
| |
| PRODUCT APPROVALS NOT SUBMITTED BEFORE |
| ISSUANCE WILL REQUIRE SEPARATE PERMITS |
| WITH ADDITIONAL FEES FOR THOSE ITEMS. |
| |
| 5.)FLORIDA STATEWIDE PRODUCT APPROVALS |
| OR SITE SPECIFIC REQUIRED, SEE DCA |
| WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| RULE 9B-72 EFFECTIVE OCTOBER 1, 2003. |
| |
| 6.)SUBMIT A HURRICANE INSTALLATION |
| SCHEDULE, SEE ATTACHED.IF THIS IS NOT |
| SUBMITTED BEFORE TIME OF PERMIT |
| ISSUANCE A SEPARATE PERMIT FOR THIS |
| ITEM WILL BE REQUIRED. |
| |
| 7.)PROVIDE THE IMPACT FEE STAMP.THE |
| RECEIPT IS IN THE PACKAGE BUT THE PLANS |
| ARE NOT STAMPED. |
| |
| 8.)PROVIDE A SOILS INVESTIGATION |
| REPORT. |
| |
| 9.)PROVIDE AREA CALCULATIONS FOR |
| EACH UNIT; A/C AREA, NON A/C AREA, AND |
| TOTAL. |