2004-02-02 00:00:00BUILDING PLAN REVIEW: FAILED!!
  
  
 1. SURVEY SAYS STRUCTURE IS IN A "B"
 ZONE. MAPS SHOW "AO" REQUIRING A
 COMPLETED ELEVATION CERTIFICATE.
  
 2. THE TYPE OF CONSTRUCTION SHOWN ON
 SHEET A0.01 HAS BEEN CHANGED TO TYPE
 V. ACCORDING TO TABLE 600 IT SHOULD BE
 A TYPE "VI" ZONE. CORRECT NOTES.
  
 3. A SIGNED AND SEALED COPY OF THE SOIL
 REPORT MUST BE SUBMITTED.
  
 4. CORRECT DETAIL FOR GLASS BLOCK TO
 COMPLY WITH 1 HOUR ASSEMBLY ON ZERO LOT
 LINE.
  
 5. PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 6. TERMITE PROTECTION: A SOIL BAIT
 TREATMENT IS THE METHOD DESCRIBED IN
 SEC. 1816.1.7.A SIGNED CONTRACT IS
 REQUIRED TO BE SUBMITTED ASSURING THE
 INSTALLATION, MAINTENANCE, & MONITORING
 OF THE BAITING SYSTEM FOR A MINIUM OF
 FIVE (5) YEARS. SEE FBC 1816 TERMITE
 PROTECTION.
  