2004-02-02 00:00:00 | BUILDING PLAN REVIEW: FAILED!! |
| |
| |
| 1. SURVEY SAYS STRUCTURE IS IN A "B" |
| ZONE. MAPS SHOW "AO" REQUIRING A |
| COMPLETED ELEVATION CERTIFICATE. |
| |
| 2. THE TYPE OF CONSTRUCTION SHOWN ON |
| SHEET A0.01 HAS BEEN CHANGED TO TYPE |
| V. ACCORDING TO TABLE 600 IT SHOULD BE |
| A TYPE "VI" ZONE. CORRECT NOTES. |
| |
| 3. A SIGNED AND SEALED COPY OF THE SOIL |
| REPORT MUST BE SUBMITTED. |
| |
| 4. CORRECT DETAIL FOR GLASS BLOCK TO |
| COMPLY WITH 1 HOUR ASSEMBLY ON ZERO LOT |
| LINE. |
| |
| 5. PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, |
| 2003 ARE REQUIRED TO COMPLY WITH THE |
| FLORIDA PRODUCT APPROVAL SYSTEM. FOR |
| INFORMATIONPLEASE SEE THE STATE WEBSITE |
| AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. |
| |
| 6. TERMITE PROTECTION: A SOIL BAIT |
| TREATMENT IS THE METHOD DESCRIBED IN |
| SEC. 1816.1.7.A SIGNED CONTRACT IS |
| REQUIRED TO BE SUBMITTED ASSURING THE |
| INSTALLATION, MAINTENANCE, & MONITORING |
| OF THE BAITING SYSTEM FOR A MINIUM OF |
| FIVE (5) YEARS. SEE FBC 1816 TERMITE |
| PROTECTION. |
| |
| ANY QUESTIONS PLEASE CALL: |
| LEA SMITH, BUILDING PLANS EXAMINER |
| 805-6713 |