2004-02-23 00:00:00DENIED
  
 1) THE STRUCTURE IS LOCATED IN AN "AO"
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2) 1001.1.3/ 1005.4 ZERO LOT LINE
 EGRESS:WHEN ACCESS TO OR FROM A RE-
 QUIRED EMERGENCY ESCAPE AND RESCUE OPEN-
 ING OF A STRUCTURE TO THE PUBLIC WAY,
 REQUIRES TRANSVERSING A PROPERTY
 (ADJOINING LOT) THAT IS NOT PART OF THE
 ONE WHICH THE STRUCTURE IS LOCATED, AN
 EGRESS EASEMENT THROUGH THE ADJOINING
 PROPERTY IS REQUIRED AND SHALL BE RECORD
 ED IN THE COUNTY RECORDS. THIS EASEMENT
 SHALL BE A MINIMUM OF 3' WIDE AND NOTH-
 ING SHALL BE PLACED WITHIN THE EASEMENT
 AREA WHICH WOULD BLOCK ACCESS TO THE
 EASEMENT AND OR IMPEDE EMERGENCY EGRESS
 FROM THE RESCUE OPENING TO THE PUBLIC
 WAY. NO LANDSCAPING, FENCES OR OTHER
 IMPEDIMENTS SHALL BE INSTALLED IN THIS
 EASEMENT. SUBMIT A RECORDED COPY OF THE
 SUBDIVISION COVENENTS THAT SPECIFY AN
 EMERGENCY EGRESS AS INDICATED ABOVE.
  
 3)THE PLANS DO NOT SPECIFY A TRANSOM
 WINDOW ABOVE THE ENTRY DOOR. THE STORM
 PANEL KEY PLAN AND INSTALLATION SCHEDULE
 INDICATE A WINDOW AT THIS LOCATION.
 PLEASE CLARIFY.
  
 4) THE PRODUCT APPROVAL FOR THE STORM
 PANELS IS MISSING THE SBCCI EVALUATION
 REPORT.
  
 5) SOME OF THE PANEL SPANS LISTED ON THE
 STORM PANEL SCHEDULE ARE LESS THAN THE
 MINIMUM PANEL LENGTHS SPECIFIED IN TABLE
 5 OF THE PRODUCT APPROVAL. PLEASE
 CORRECT.
  
 6) THE LOCAL PRODUCT APPROVAL FORMS THAT
 WERE SUBMITTED DO NOT LIST A QUALITY
 ASSURANCE ENTITY. PLEASE CORRECT.
  
 7) THE NOA NUMBER ON THE LOCAL PRODUCT
 APPROVAL FORM FOR THE FIXED WINDOW DOES
 NOT MATCH THE MIAMI-DADE NOA THAT IS
 ATTACHED.
  
 8) THE STATE PRODUCT APPROVAL SHEET FOR
 THE FIREDOOR,LLC DOES NOT MATCH THE
 THERMA-TRU NOA THAT IS ATTACHED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714