2004-02-23 00:00:00 | DENIED |
| |
| 1) THE STRUCTURE IS LOCATED IN AN "AO" |
| ZONE AN ELEVATION CERTIFICATE WILL BE |
| REQUIRED. |
| |
| 2) 1001.1.3/ 1005.4 ZERO LOT LINE |
| EGRESS:WHEN ACCESS TO OR FROM A RE- |
| QUIRED EMERGENCY ESCAPE AND RESCUE OPEN- |
| ING OF A STRUCTURE TO THE PUBLIC WAY, |
| REQUIRES TRANSVERSING A PROPERTY |
| (ADJOINING LOT) THAT IS NOT PART OF THE |
| ONE WHICH THE STRUCTURE IS LOCATED, AN |
| EGRESS EASEMENT THROUGH THE ADJOINING |
| PROPERTY IS REQUIRED AND SHALL BE RECORD |
| ED IN THE COUNTY RECORDS. THIS EASEMENT |
| SHALL BE A MINIMUM OF 3' WIDE AND NOTH- |
| ING SHALL BE PLACED WITHIN THE EASEMENT |
| AREA WHICH WOULD BLOCK ACCESS TO THE |
| EASEMENT AND OR IMPEDE EMERGENCY EGRESS |
| FROM THE RESCUE OPENING TO THE PUBLIC |
| WAY. NO LANDSCAPING, FENCES OR OTHER |
| IMPEDIMENTS SHALL BE INSTALLED IN THIS |
| EASEMENT. SUBMIT A RECORDED COPY OF THE |
| SUBDIVISION COVENENTS THAT SPECIFY AN |
| EMERGENCY EGRESS AS INDICATED ABOVE. |
| |
| 3)THE PLANS DO NOT SPECIFY A TRANSOM |
| WINDOW ABOVE THE ENTRY DOOR. THE STORM |
| PANEL KEY PLAN AND INSTALLATION SCHEDULE |
| INDICATE A WINDOW AT THIS LOCATION. |
| PLEASE CLARIFY. |
| |
| 4) THE PRODUCT APPROVAL FOR THE STORM |
| PANELS IS MISSING THE SBCCI EVALUATION |
| REPORT. |
| |
| 5) SOME OF THE PANEL SPANS LISTED ON THE |
| STORM PANEL SCHEDULE ARE LESS THAN THE |
| MINIMUM PANEL LENGTHS SPECIFIED IN TABLE |
| 5 OF THE PRODUCT APPROVAL. PLEASE |
| CORRECT. |
| |
| 6) THE LOCAL PRODUCT APPROVAL FORMS THAT |
| WERE SUBMITTED DO NOT LIST A QUALITY |
| ASSURANCE ENTITY. PLEASE CORRECT. |
| |
| 7) THE NOA NUMBER ON THE LOCAL PRODUCT |
| APPROVAL FORM FOR THE FIXED WINDOW DOES |
| NOT MATCH THE MIAMI-DADE NOA THAT IS |
| ATTACHED. |
| |
| 8) THE STATE PRODUCT APPROVAL SHEET FOR |
| THE FIREDOOR,LLC DOES NOT MATCH THE |
| THERMA-TRU NOA THAT IS ATTACHED. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |