Plan Review Notes
Plan Review Notes For Permit 03121198
Permit Number 03121198
Review Stop B
Sequence Number 1
Notes
Date Text
2004-02-03 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT A SIGNED AND SEALED COPY OF
 THE SOIL REPORT.
  
 3) THE STRUCTURE IS LOCATED IN AN "AO"
 FLOOD ZONE. AN ELEVATION CERTIFICATE
 WILL BE REQUIRED.
  
 4) THE SURVEY LISTS THE INCORRECT FLOOD
 ZONE AND THE WRONG FIRM MAP NUMBER.
 SUBMIT A CORRECTED SURVEY.
  
 5)1001.1.3/ 1005.4 ZERO LOT LINE
 EGRESS:WHEN ACCESS TO OR FROM A RE-
 QUIRED EMERGENCY ESCAPE AND RESCUE OPEN-
 ING OF A STRUCTURE TO THE PUBLIC WAY,
 REQUIRES TRANSVERSING A PROPERTY
 (ADJOINING LOT) THAT IS NOT PART OF THE
 ONE WHICH THE STRUCTURE IS LOCATED, AN
 EGRESS EASEMENT THROUGH THE ADJOINING
 PROPERTY IS REQUIRED AND SHALL BE RECORD
 ED IN THE COUNTY RECORDS. THIS EASEMENT
 SHALL BE A MINIMUM OF 3' WIDE AND NOTH-
 ING SHALL BE PLACED WITHIN THE EASEMENT
 AREA WHICH WOULD BLOCK ACCESS TO THE
 EASEMENT AND OR IMPEDE EMERGENCY EGRESS
 FROM THE RESCUE OPENING TO THE PUBLIC
 WAY. NO LANDSCAPING, FENCES OR OTHER
 IMPEDIMENTS SHALL BE INSTALLED IN THIS
 EASEMENT.
  
 6) SHEET A0.01 LISTS THE CONSTRUCTION
 TYPE III. BASED ON FBC TABLE 600 AND THE
 PLANS THE CONSTRUCTION IS TYPE VI.
  
 7) NOTE 22 ON A0.01 REFERS TO FBC
 1816.1.7, WHICH IS FOR TERMITE BAITING
 SYSTEMS. PLEASE CLARIFY. NOTE: A SIGNED
 CONTRACT PAID IN FULL FOR 5 YEARS FROM
 THE DATE OF CO IS REQUIRED BEFORE THE
 SLAB IS POURED.
  
 8) REVISE THE DRYWALL FASTENING NOTE ON
 A3.01. THE FASTENER SPACING FOR SCREWS
 IS NOT MORE THAN 12"OC PER FBC 2504.4.1
 AND GA 216.
  
 9) REVISE DETAIL 2 ON A4.01 TO SHOW
 FIREBLOCKING WHERE THE WALL AND CEILING
 MEET. SEE FBC 2305.1.
  
 10) REVISE THE GLASS BLOCK DETAIL 10 ON
 A4.02 TO A ONE HOUR FIRE RATED ASSEMBLY.
 SEE UL R2556.
  
 11) SPECIFY THE ATTIC LIVE LOADS ON S2.
 FBC TABLE 1604.1 REQUIRES 30PSF FOR
 ATTICS WITH STORAGE AND 10PSF FOR ATTICS
 WITHOUT STORAGE.
  
 12) THE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS INDICATE
 A GLAZED WINDOW ABOVE THE ENTRY DOORS.
 THIS IS NOT SHOWN ON THE PLANS. PLEASE
 CLARIFY.
  
 13) ITEM #4 IN THE DOOR SCHEDULE IS
 LISTED AS A 6'- 8" WIDE SLIDING GLASS
 DOOR AND THE FLOOR PLAN SHOWS A 6' WIDE
 OPENING. PLEASE CORRECT.
  
 14) THE KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS CONTAIN
 SOME ERRORS. CHECK THE OPENING SIZES AND
 MINIMUM PANEL LENGTH AS LISTED IN THE
 PRODUCT APPROVAL. PLEASE CORRECT.
  
 15) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714