2004-02-03 00:00:00 | DENIED |
| |
| 1) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2) SUBMIT A SIGNED AND SEALED COPY OF |
| THE SOIL REPORT. |
| |
| 3) THE STRUCTURE IS LOCATED IN AN "AO" |
| FLOOD ZONE. AN ELEVATION CERTIFICATE |
| WILL BE REQUIRED. |
| |
| 4) THE SURVEY LISTS THE INCORRECT FLOOD |
| ZONE AND THE WRONG FIRM MAP NUMBER. |
| SUBMIT A CORRECTED SURVEY. |
| |
| 5)1001.1.3/ 1005.4 ZERO LOT LINE |
| EGRESS:WHEN ACCESS TO OR FROM A RE- |
| QUIRED EMERGENCY ESCAPE AND RESCUE OPEN- |
| ING OF A STRUCTURE TO THE PUBLIC WAY, |
| REQUIRES TRANSVERSING A PROPERTY |
| (ADJOINING LOT) THAT IS NOT PART OF THE |
| ONE WHICH THE STRUCTURE IS LOCATED, AN |
| EGRESS EASEMENT THROUGH THE ADJOINING |
| PROPERTY IS REQUIRED AND SHALL BE RECORD |
| ED IN THE COUNTY RECORDS. THIS EASEMENT |
| SHALL BE A MINIMUM OF 3' WIDE AND NOTH- |
| ING SHALL BE PLACED WITHIN THE EASEMENT |
| AREA WHICH WOULD BLOCK ACCESS TO THE |
| EASEMENT AND OR IMPEDE EMERGENCY EGRESS |
| FROM THE RESCUE OPENING TO THE PUBLIC |
| WAY. NO LANDSCAPING, FENCES OR OTHER |
| IMPEDIMENTS SHALL BE INSTALLED IN THIS |
| EASEMENT. |
| |
| 6) SHEET A0.01 LISTS THE CONSTRUCTION |
| TYPE III. BASED ON FBC TABLE 600 AND THE |
| PLANS THE CONSTRUCTION IS TYPE VI. |
| |
| 7) NOTE 22 ON A0.01 REFERS TO FBC |
| 1816.1.7, WHICH IS FOR TERMITE BAITING |
| SYSTEMS. PLEASE CLARIFY. NOTE: A SIGNED |
| CONTRACT PAID IN FULL FOR 5 YEARS FROM |
| THE DATE OF CO IS REQUIRED BEFORE THE |
| SLAB IS POURED. |
| |
| 8) REVISE THE DRYWALL FASTENING NOTE ON |
| A3.01. THE FASTENER SPACING FOR SCREWS |
| IS NOT MORE THAN 12"OC PER FBC 2504.4.1 |
| AND GA 216. |
| |
| 9) REVISE DETAIL 2 ON A4.01 TO SHOW |
| FIREBLOCKING WHERE THE WALL AND CEILING |
| MEET. SEE FBC 2305.1. |
| |
| 10) REVISE THE GLASS BLOCK DETAIL 10 ON |
| A4.02 TO A ONE HOUR FIRE RATED ASSEMBLY. |
| SEE UL R2556. |
| |
| 11) SPECIFY THE ATTIC LIVE LOADS ON S2. |
| FBC TABLE 1604.1 REQUIRES 30PSF FOR |
| ATTICS WITH STORAGE AND 10PSF FOR ATTICS |
| WITHOUT STORAGE. |
| |
| 12) THE KEY PLAN AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS INDICATE |
| A GLAZED WINDOW ABOVE THE ENTRY DOORS. |
| THIS IS NOT SHOWN ON THE PLANS. PLEASE |
| CLARIFY. |
| |
| 13) ITEM #4 IN THE DOOR SCHEDULE IS |
| LISTED AS A 6'- 8" WIDE SLIDING GLASS |
| DOOR AND THE FLOOR PLAN SHOWS A 6' WIDE |
| OPENING. PLEASE CORRECT. |
| |
| 14) THE KEY PLAN AND INSTALLATION |
| SCHEDULE FOR THE STORM PANELS CONTAIN |
| SOME ERRORS. CHECK THE OPENING SIZES AND |
| MINIMUM PANEL LENGTH AS LISTED IN THE |
| PRODUCT APPROVAL. PLEASE CORRECT. |
| |
| 15) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |