Plan Review Notes
Plan Review Notes For Permit 03121194
Permit Number 03121194
Review Stop B
Sequence Number 1
Notes
Date Text
2004-02-02 00:00:00BUILDING PLAN REVIEW: FAILED!!
  
 1. NO RECEIPT SUBMITTED FOR IMPACT FEES
 PAID TO PBC. (PLANS ARE STAMPED BY PBC)
  
 2. LOT IS LOCATED IN A "AO" FLOOD ZONE.
 AN ELEVATIONCERTIFICATE WILL BE
 REQUIRED BEFORE C/O.
  
 3. A SIGNED & SEALED SOIL REPORT MUST BE
 SUBMITTED.
  
 4. CORRECT DETAIL FOR GLASS BLOCK IN A
 1 HOUR ASSEMBLY ON ZERO LOT LINE.
  
 5. PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1,
 2003ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATIONPLEASE SEE THE STATE WEBSITE
 AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6. GENERAL NOTES (A0.01) #22 DESCRIBES
 TERMITE PROTECTION TO BE A SOIL BAIT
 TREATMENT METHOD. A SIGNED CONTRACT IS
 REQUIRED TO BE SUBMITTED ASSURING THE
 INSTALLATION, MAINTENANCE & MONITORING
 OF THE BAITING SYSTEM FOR A MINIUM OF 5
 YEARS. SEE FBC 1816 TERMITE PROTECTION.
 PLANS REFERENCE 1816.1.7.
  
 7. ONLY 1 COPY OF THEFLORIDA ENERGY
 CODE WAS SUBMITTED.SUBMIT ANOTHER SET
 AND 1 EXTRA COPY OF PAGE 1.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 805-6713