Plan Review Notes
Plan Review Notes For Permit 03121171
Permit Number 03121171
Review Stop E
Sequence Number 1
Notes
Date Text
2003-12-29 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE HAVE PLANS SIGNED, DATED
 BY ENGINEER WITH COMPLETE SIGNATURE
 AS PER FS 471.025 AND FAC 61G15-23.002
 PER FBPE'S INITIALS ARE NOT ACCEPTABLE
 AS SIGNATURE.
  
 2)NOTE: PLEASE SEE PLANS STILL REFERENCE
 THE 1999 NEC. THE 2002 NEC WAS ADOPTED
 BY STATE 7/1/03. PLEASE ADJUST ALL CODES
 AND NOTES ON PLANS.
  
 3)NOTE: PLEASE SEE 210.12 FOR ARC FAULT
 PROTECTION. PLEASE SEE THAT THIS HAS
 CHANGED SINCE 1999 NEC. PLEASE ADJUST
 NOTE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]