Plan Review Notes
Plan Review Notes For Permit 03121166
Permit Number 03121166
Review Stop E
Sequence Number 1
Notes
Date Text
2003-12-29 00:00:00************ UNSAT **************
  
 1)NOTE: PLANS STILL REFERENCE THE 1999
 NEC.2002 NEC WAS ADOPTED 7/1/2003.
 PLEASE ADJUST ALL CODES REF AND ADJUST
 NOTES.
  
 2)NOTE: PLEASE SEE 210.12 FOR ARC FAULT
 PROTECTION. THIS HAS CHANGE IN THE 2002
 CODE.
  
 3)NOTE: PLEASE HAVE ENGINEER OF RECORD
 SIGN PLANS WITH FULL NAME. FBPE'S HAS
 NOTED TO THIS OFFICE THAT INITIALS ARE
 NOT ACCEPTABLE. PER FS 471.025
 FAC 61G15-23.002.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]