Date |
Text |
2004-01-27 00:00:00 | DENIED |
| |
| 1) STRUCTURE IS LOCATED IN AN "AO" FLOOD |
| ZONE AN ELEVATION CERTIFICATE WILL BE |
| REQUIRED BEFORE C.O. |
| |
| 2) SUBMIT A SIGNED AND SEALED COPY OF |
| THE SOIL REPORT. |
| |
| 3) SHEET A0.01 LISTS THE CONSTRUCTION AS |
| TYPE V. BASED ON FBC TABLE 600, THE |
| CONSTRUCTION IS TYPE VI. PLEASE CORRECT. |
| |
| 4) NOTE 22 ON A0.01 REFERS TO FBC |
| 1816.1.7, WHICH IS FOR TERMITE BAITING |
| SYSTEMS. PLEASE CLARIFY. NOTE: A SIGNED |
| CONTRACT PAID IN FULL FOR FIVE YEARS |
| FROM THE DATE OF C.O. IS REQUIRED BEFORE |
| THE SLAB IS POURED. |
| |
| 5) REVISE THE DRYWALL FASTENING NOTE ON |
| A3.01 THE FASTENER SPACING FOR SCREWS IS |
| NOT MORE THAN 12"OC FOR CEILINGS AND |
| WALLS ON FRAMING 24"OC PER FBC 2504.4.1 |
| AND GA 216. |
| |
| 6) REVISE THE ROOF SHEATHING FASTENER |
| SPACING NOTE ON A1.02 TO CORRESPOND WITH |
| THE NOTES ON A3.01 AND S4. |
| |
| 7) REVISE DETAIL 2 ON A4.01 TO SHOW |
| FIREBLOCKING WHERE THE WALL AND CEILING |
| MEET PER FBC 2305.1. |
| |
| 8) REVISE THE GLASS BLOCK DETAIL 10 ON |
| A4.02 FOR A ONE HOUR FIRE RATED ASSEMBLY |
| SEE UL R2556. |
| |
| 9) SPECIFY THE LENGTH/EMBED DEPTH OF THE |
| 3/4"DIA. WEDGE ANCHOR BOLTS IN DETAIL 2 |
| ON S5 AND THE 5/8" DIA. W.A. BOLTS IN |
| SECTIONS E-E AND F-F ON S5. |
| |
| 10) SPECIFY THE ATTIC LIVE LOADS ON S2. |
| FBC TABLE 1604.1 REQUIRES 30PSF FOR |
| ATTICS WITH STORAGE AND 10PSF FOR ATTICS |
| WITHOUT STORAGE. |
| |
| 11) THE KEY PLAN AND INSTALLATION |
| SCHEDULES FOR THE STORM PANELS DO NOT |
| MATCH THE PLANS. CHECK NUMBER AND SIZES |
| OF OPENINGS. |
| |
| 12) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |