2004-01-22 00:00:00 | DENIED |
| |
| 1) STRUCTURE IS LOCATED IN AN "AO" FLOOD |
| ZONE AN ELEVATION CERTIFICATE WILL BE |
| REQUIRED. |
| |
| 2) SUBMIT A COPY OF THE PAID RECIEPT FOR |
| THE IMPACT FEES. |
| |
| 3) THE GLASS BLOCK IN THE WALL ON THE |
| ZERO LOT LINE IS REQUIRED TO HAVE A ONE |
| HOUR FIRE RATING. SEE FBC TABLE 600, |
| WHICH REQUIRES THE EXTERIOR WALL TO HAVE |
| A ONE HOUR FIRE RATING AND HAVE NO |
| OPENINGS. |
| |
| 4) SUBMIT A SIGNED AND SEALED COPY OF |
| THE SOIL REPORT. |
| |
| 5) SHEET A0.01 LISTS THE CONSTRUCTION AS |
| TYPE III. BASED ON FBC TABLE 600, THE |
| CONSTRUCTION IS TYPE VI. PLEASE CORRECT. |
| |
| 6) NOTE 22 ON A0.01 REFERENCES FBC |
| 1816.1.7, WHICH IS FOR TERMITE BAITING |
| SYSTEMS. PLEASE CLARIFY. NOTE: A SIGNED |
| CONTRACT FOR A MINIMUM OF 5 YEARS FROM |
| THE DATE OF THE C.O. THAT HAS BEEN PAID |
| IS REQUIRED BEFORE THE SLAB IS POURED. |
| |
| 7) REVISE THE GYPSUM FASTENING NOTE ON |
| A3.01. THE NAIL SPACING FOR SINGLE |
| NAILING IS 7"OC FOR CEILINGS AND 8"OC |
| FOR WALLS. THE SPACING FOR SCREWS IS NOT |
| MORE THAN 12"OC FOR WALLS AND CEILINGS |
| WHEN FRAMING IS 24"OC. SEE FBC 2504.4.1 |
| AND GA 216. |
| |
| 8) SPECIFY ON THE PLAN IN A CONSPICUOUS |
| LOCATION THAT THE DEN IS NOT TO BE USED |
| AS A SLEEPING ROOM. |
| |
| 9) REVISE DETAIL 2 ON A4.01 TO SHOW |
| FIREBLOCKING WHERE THE WALL AND CEILING |
| MEET PER FBC 2305.1. |
| |
| 10) DETAIL 10 ON A4.02 IS NOT FOR A FIRE |
| RATED GLASS BLOCK ASSEMBLY. PLEASE |
| REVISE. SEE UL R2556. |
| |
| 11) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 12) SPECIFY THE ATTIC LIVE LOAD ON S2. |
| FBC TABLE 1604.1 REQUIRES 30PSF FOR |
| ATTICS WITH STORAGE AND 10PSF FOR ATTICS |
| WITHOUT STORAGE. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |