Plan Review Notes
Plan Review Notes For Permit 03121144
Permit Number 03121144
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-22 00:00:00DENIED
  
 1) STRUCTURE IS LOCATED IN AN "AO" FLOOD
 ZONE AN ELEVATION CERTIFICATE WILL BE
 REQUIRED.
  
 2) SUBMIT A COPY OF THE PAID RECIEPT FOR
 THE IMPACT FEES.
  
 3) THE GLASS BLOCK IN THE WALL ON THE
 ZERO LOT LINE IS REQUIRED TO HAVE A ONE
 HOUR FIRE RATING. SEE FBC TABLE 600,
 WHICH REQUIRES THE EXTERIOR WALL TO HAVE
 A ONE HOUR FIRE RATING AND HAVE NO
 OPENINGS.
  
 4) SUBMIT A SIGNED AND SEALED COPY OF
 THE SOIL REPORT.
  
 5) SHEET A0.01 LISTS THE CONSTRUCTION AS
 TYPE III. BASED ON FBC TABLE 600, THE
 CONSTRUCTION IS TYPE VI. PLEASE CORRECT.
  
 6) NOTE 22 ON A0.01 REFERENCES FBC
 1816.1.7, WHICH IS FOR TERMITE BAITING
 SYSTEMS. PLEASE CLARIFY. NOTE: A SIGNED
 CONTRACT FOR A MINIMUM OF 5 YEARS FROM
 THE DATE OF THE C.O. THAT HAS BEEN PAID
 IS REQUIRED BEFORE THE SLAB IS POURED.
  
 7) REVISE THE GYPSUM FASTENING NOTE ON
 A3.01. THE NAIL SPACING FOR SINGLE
 NAILING IS 7"OC FOR CEILINGS AND 8"OC
 FOR WALLS. THE SPACING FOR SCREWS IS NOT
 MORE THAN 12"OC FOR WALLS AND CEILINGS
 WHEN FRAMING IS 24"OC. SEE FBC 2504.4.1
 AND GA 216.
  
 8) SPECIFY ON THE PLAN IN A CONSPICUOUS
 LOCATION THAT THE DEN IS NOT TO BE USED
 AS A SLEEPING ROOM.
  
 9) REVISE DETAIL 2 ON A4.01 TO SHOW
 FIREBLOCKING WHERE THE WALL AND CEILING
 MEET PER FBC 2305.1.
  
 10) DETAIL 10 ON A4.02 IS NOT FOR A FIRE
 RATED GLASS BLOCK ASSEMBLY. PLEASE
 REVISE. SEE UL R2556.
  
 11) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 12) SPECIFY THE ATTIC LIVE LOAD ON S2.
 FBC TABLE 1604.1 REQUIRES 30PSF FOR
 ATTICS WITH STORAGE AND 10PSF FOR ATTICS
 WITHOUT STORAGE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714