Plan Review Notes For Permit 03121093 |
Permit Number |
03121093 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2004-02-02 00:00:00 | PROVISO: | | DUCT SMOKE DETECTORS REQUIRED FOR AHU'S | | #3 & 7, PER 2001 FBC(M) 606.2.1. | | PLEASE PROVIDE DUCT SMOKE DETECTORS IN | | THE SUPPLY AIR DUCT OF THESE TWO SYSTEMS | | AND ANY OTHERS THAT HAVE THE DESIGN | | CAPACITY GREATER THAN 2,000 CFM. | | | | NOTIFICATION TO ALARM/STROBE REQUIRED | | PER NFPA 90A 4-4.4.3. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|