Plan Review Notes
Plan Review Notes For Permit 03121093
Permit Number 03121093
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-02 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SEE THAT PLANS ARE REQ'D
 TO HAVE COMPLETE SIGNATURE BY THE
 ENGINEER OF RECORD. PEER FS 471.025 AND
 FAC 61G15-23.002.
 ONE SET OF PLANS ARE BEING REATINED FOR
 RECORD FOR ABOVE MENTION.
  
 2)NOTE: PLEASE SHOW LOCATION OF PANEL
 "L1A" ON PLANS.
  
 3)NOTE: PLEASE SHOW ANY/ALL CONTINOUS
 LOADS AT 125%, 215.3, 230.42 ETC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]