2004-01-14 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03121093 |
| ADD: 2301 CENTREPARK WEST DR/ 100 |
| CONT: LEIGHTON MC GINN |
| TEL: (561)722-9696 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1ST REVIW |
| ACTION: DENIED |
| |
| 1) PLANS DRAWN TO 1/4" SCALE, BUT ARE |
| ACTUALLY 1/8" SCALE, FLOOR PLAN A-1. |
| |
| 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) OVERHEAD DOOR |
| B) EXTERIOR SWING DOOR |
| |
| 3) PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 4) BOTH OF THE ABOVE OPENINGS ARE NEW |
| OPENINGS, NO INFORMATION ON LENTALS OR |
| COLUMNS. |
| |
| 5)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| DOOR# 16, PLEASE PROVIDE INFO ON ELEC |
| LOCK, FOR LOSS OF POWER ARE THEY FAIL |
| SAFE OPEN OR CLOSED? |
| |
| 6)1204.2 SURROUNDING MATERIALS; |
| THE WALLS & FLOORS OF ALL PUBLIC REST- |
| ROOMS SHALL BE LINED WITH NONABSORBANT |
| MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| FLOOR. |
| |
| 7) OFFICE DOOR# 107, |
| 11-4.13.6 MANEUVERING CLEARENCES |
| AT DOORS. MINIMUM MANEUVERING CLEARENCES |
| AT DOORS THAT ARE NOT AUTOMATIC OR |
| POWER-ASSISTED SHALL BE AS SHOWN IN |
| FIG. 25. THE FLOOR OR GROUND AREA WITH |
| IN THE REQUIRED CLEARENCES SHALL BE |
| CLEAR & LEVEL. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |