Plan Review Notes For Permit 03121047 |
Permit Number |
03121047 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-12-24 00:00:00 | ************** UNSAT ***************** | | | | 1)NOTE: PLANS STILL REFERENCE THE 1999 | | NEC. PLEASE SEE THAT CODE CHANGED ON | | 7/1/03. PLEASE SEE THAT ALL CODES REF | | ON PLANS SHOULD CORRELATE WITH 2002 #`S. | | | | | | 2)NOTE: PLEASE SEE 210.12 /2002 NEC. | | THIS HAS CHANGED FROM 99 NEC. | | | | 3)NOTE: PLANS ARE REQ'D TO BE SIGNED | | W/ A COMPLETE SIGNATURE FROM ENGINEER | | OF RECORD. INITIALS ARE NOT ACCEPTABLE | | PER THE FBPE'S. PER FS 471.025 AND FAC | | 61G15-23.002 | | | | PLEASE ADJUST PLANS. | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|