2003-12-24 00:00:00 | ************** UNSAT ******************* | | | | 1)NOTE: PLEASE SEE THAT PLANS STILL | | REFERENCE 1999. PLEASE ADJUST ALL CODES | | TO CORRELATE WITH 2002 NEC. | | | | 2)NOTE: PLEASE SEE 210.12, ARC FAULT | | PROTECTION REQUIREMENT HAS COMPLETELY | | CHANGED. | | | | 3)NOTE: PLEASE SIGN PLANS WITH COMPLETE | | SIGNATURE . FBPE'S MENTIONS INITIALS | | ARE NOT ACCEPTABLE. PER FS 471.025 AND | | FAC 61G15-23.002 | | | | PLEASE ADJUST | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|