Plan Review Notes
Plan Review Notes For Permit 03121046
Permit Number 03121046
Review Stop E
Sequence Number 1
Notes
Date Text
2003-12-24 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE SEE THAT PLANS STILL
 REFERENCE 1999. PLEASE ADJUST ALL CODES
 TO CORRELATE WITH 2002 NEC.
  
 2)NOTE: PLEASE SEE 210.12, ARC FAULT
 PROTECTION REQUIREMENT HAS COMPLETELY
 CHANGED.
  
 3)NOTE: PLEASE SIGN PLANS WITH COMPLETE
 SIGNATURE . FBPE'S MENTIONS INITIALS
 ARE NOT ACCEPTABLE. PER FS 471.025 AND
 FAC 61G15-23.002
  
 PLEASE ADJUST
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]