Plan Review Notes
Plan Review Notes For Permit 03121040
Permit Number 03121040
Review Stop E
Sequence Number 2
Notes
Date Text
2004-03-01 00:00:00*************** UNSAT ***********
  
 1)NOTE: PLEASE SEE COMMENTS FROM FIRST
 REVIEW.
  
  
 2)NOTE: PLEASE PROVIDE ADDRESS IN TITLE
 BLOCK/LOT #MIN FOR SITE. AS REQ'D UNDER
 FAC 61G1-16.004.
  
 3)NOTE: PLEASE HAVE ALL CIRCUITING
 CONFORM TO THE 2002 NEC FOR ARC FAULT
 PROTECTION. 210.12CIRCUITS#'S 13,15
  
 4))NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2
 ALL SD'S ARE REQ'D TO BE WIRED INLINE,
 HOWEVER, SD'D ARE NOW SHOWN ON SEPARATE
 CIRCUITS?
  
 5)NOTE: PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND INSERT NEW ONLY.
  
 PLANS/PERMIT APPLICATION/COMPUTER WILL
 NO LONGER REFERENCE MASTER SINCE THE
 CODE CHANGED 7/1/03
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]