Notes
Date Text
2004-01-21 00:00:00*****PROVISO/CORRECTIONS******
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 ADDRESS ALL BUILDING CORRECTIONS AT THIS
 TIME IF THE PLANS DO NOT PASS OTHER
 TRADES!!!
  
 COMMENTS ALSO APPLY TO 03121105,
 03121071,03121087, 03121095, 03121058
  
 1.)THE NOTICE OF COMMENCEMENT IS
 EXPIRED FS713.13 (90 DAYS WITHOUT
 COMMENCING WORK).
  
 2.)S-1, WATERSTOP TO BE 1 1/2" CITY OF
 WEST PALM BEACH AMENDMENTS TO THE FBC
 2111.1.9.CHECK ALL DETAILS.
  
 3.)BOTTOM CHORD LIVE LOAD IS REQUIRED
 TO BE 10, 30 IN ATTICS WITH STORAGE,
 FBC TABLE 1604.1., (SHEET S8, #9).
  
 THE FOLLOWING COMMENTS MUST BE
 ADDRESSED BEFORE THE PERMIT CAN BE
 ISSUED - NO PROVISO
  
 4.)MANY PRODUCT APPROVALS WERE
 SUBMITTED FOR ITEMS WHICH DO NOT APPEAR
 ON THE PLAN.PRODUCT APPROVALS FOR
 FIXED GLASS AND SINGLE HUNG WINDOWS
 WERE SUBMITTED, BUT NOT FOR HORIZONTAL
 SLIDERS (THE ONLY WINDOW SHOWN ON THE
 PLAN).SUBMIT ONLY PRODUCT APPROVALS
 FOR DOORS, WINDOWS, AND ROOF WHICH
 APPEAR ON THE PLAN.
  
 PRODUCT APPROVALS NOT SUBMITTED BEFORE
 ISSUANCE WILL REQUIRE SEPARATE PERMITS
 WITH ADDITIONAL FEES FOR THOSE ITEMS.
  
 5.)FLORIDA STATEWIDE PRODUCT APPROVALS
 OR SITE SPECIFIC REQUIRED, SEE DCA
 WEBSITE AT WWW.FLORIDABUILDING.ORG.
 RULE 9B-72 EFFECTIVE OCTOBER 1, 2003.
  
 6.)SUBMIT A HURRICANE SHUTTER
 INSTALLATION SCHEDULE, SEE ATTACHED.IF
 THIS IS NOT SUBMITTED BEFORE TIME OF
 PERMIT ISSUANCE A SEPARATE PERMIT FOR
 THIS ITEM WILL BE REQUIRED.
  
 7.)PROVIDE AREA CALCULATIONS FOR
 EACH UNIT TYPE - A/C SPACE, NON A/C
 SPACE, TOTAL.
  
 8.)PROVIDE A SOILS INVESTIGATION
 REPORT.