Plan Review Notes
Plan Review Notes For Permit 03121040
Permit Number 03121040
Review Stop M
Sequence Number 1
Notes
Date Text
2004-02-02 00:00:00DENIED
 COMMENTS PERTAIN TO THE FOLLOWING PERMIT
 NUMBERS:03121040, 03121058, 03121095,
 03121087, 03121071, 03121105
  
 MODEL A, B, & C
 1.PROVIDE OUTSIDE AIR CALCULATIONS PER
 2001 FBC(M) 402.2 OR 403.3.
  
 2.RETURN AIR TRANSFER GRILLE FROM THE
 MASTER BEDROOM IS NOT SIZED PROPERLY.
 REFERENCE 2001 FBC(M) 601.4 EXCEPTION #2
 AND 3. GRILLES SHALL HAVE 50 SQ INCHES
 TO 100 CFM OF SUPPLY AIR. FOR PROPER
 SIZING FOR THE RETURN TRANSFER GRILLE TO
 THE MASTER BEDROOM, ALL SUPPLY AIR TO
 THE SUITE IS TO BE INCLUDED IN THE
 CALCULATION.PLEASE REVISE.
  
 3.AUXILIARY DRAIN PAN REQUIRED PER
 2001 FBC(M) 307.2.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.