Plan Review Notes
Plan Review Notes For Permit 03121040
Permit Number 03121040
Review Stop E
Sequence Number 1
Notes
Date Text
2004-01-29 00:00:00*************** UNSAT ***********
  
 1)NOTE: PLEASE PROVIDE ADDRESS ON PLANS
 AS REQ'D UNDER FAC 61G1-16.004
  
 2)NOTE: PLEASE SEE NOTES ON PLANS
 REFERENCE THE 1999 NEC AND THE SFBC
 WHICH NEITHER ONE IS ANY LONGER IN
 EFFECT. PLEASE ADJUST PLANS AND ALL
 CODE #'S TO CORRELATE TO 2002 NEC.
  
 3)NOTE: PLEASE PROVIDE CIRCUITING'S ON
 PLANS AND PANEL SCHEDULE IN ORDER TO
 PROVIDE REQ'D ARC FAULT PROTECTION PER
 THE 2002 NEC. PLANS NOW SHOW WHAT IS
 REQ'D UNDER THE 1999 NEC.
  
 4)NOTE: PLEASE SEE CODE REFERENCED FOR
 GROUNDING ELECTRODE SYSTEM. CODES ARE
 FOR 1999 NEC. PLEASE SEE 2002
  
 5)NOTE: PLEASE SEE NOTES FROM OTHER
 REVIEWERS.
  
 PLEASE REMOVE ALL OLD/ VOIDED SHEETS
 AND INSERT NEW SHEETS INTO TWO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  