| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} PLEASE NOTE THAT OFFICE AREAS ARE TO |
| BE CALCULATED PER 220.3(A). |
| |
| 2} PLEASE SHOW LOAD CALCULATIONS, |
| PLEASE SHOW PER: |
| 220.3,220.10,220.11,220.13 ETC. |
| PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| AT 125% PER 215.2(A)(1),210.19(A)(1) & |
| 210.20(A). |
| |
| 3} PANEL "A" CALCULATION REMAINS THE |
| SAME AS ON THE PERMITED SET OF PLANS, |
| BUT ACCORDING TO THE REVISION SET THERE |
| ARE IS LIGHTING AND RECEPTACLE LOADS |
| ADDED, PLEASE CORRECT. |
| |
| 4} PANEL "B" HAD A ROLLUP DOOR REMOVED |
| FROM THE PANEL , PLEASE INDICATE WHERE |
| IT IS BEING FED FROM, INCLUDE IT ON A |
| SCHEDULE AND IN THE LOAD CALC'S. |
| |
| 5} PANEL "C" IS BEING FED FROM THE MAIN |
| PANEL ON THE RISER DIAGRAM, BUT IS NOT |
| ON THAT PANEL.SCHEDULE, NO OCP OR WIRE |
| SIZE LISTED. PLEASE SHOW HOW FED. |
| |