Plan Review Notes
Plan Review Notes For Permit 03121021
Permit Number 03121021
Review Stop E
Sequence Number 3
Notes
Date Text
2004-03-31 00:00:00 
 PLEASE NOTE THAT THE BUILDING PLAN HAS
 CHANGED. THERE CAN BE NO ELECTRICAL
 PLANS SUBMITTED FOR REVIEW PRIOR TO THE
 BUILDING PLAN BEING SUBMITTED FOR
 REVIEW.
 ALL PLANS MAY BE SUBMITTED TOGETHER TO
 EXPEDITE THE REVIEW PROCESS.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE NOTE THAT OFFICE AREAS ARE TO
 BE CALCULATED PER 220.3(A).
  
 2} PLEASE SHOW LOAD CALCULATIONS,
 PLEASE SHOW PER:
 220.3,220.10,220.11,220.13 ETC.
 PLEASE ALSO SHOW ALL CONTINOUS LOADS
 AT 125% PER 215.2(A)(1),210.19(A)(1) &
 210.20(A).
  
 3} PANEL "A" CALCULATION REMAINS THE
 SAME AS ON THE PERMITED SET OF PLANS,
 BUT ACCORDING TO THE REVISION SET THERE
 ARE IS LIGHTING AND RECEPTACLE LOADS
 ADDED, PLEASE CORRECT.
  
 4} PANEL "B" HAD A ROLLUP DOOR REMOVED
 FROM THE PANEL , PLEASE INDICATE WHERE
 IT IS BEING FED FROM, INCLUDE IT ON A
 SCHEDULE AND IN THE LOAD CALC'S.
  
 5} PANEL "C" IS BEING FED FROM THE MAIN
 PANEL ON THE RISER DIAGRAM, BUT IS NOT
 ON THAT PANEL.SCHEDULE, NO OCP OR WIRE
 SIZE LISTED. PLEASE SHOW HOW FED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026