Plan Review Notes For Permit 03121021 |
Permit Number |
03121021 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2003-12-30 00:00:00 | *************** UNSAT ************ | | | | 1)NOTE: PLEASE CORRELATECIRCUITS #'S | | ON PLANS AND PANEL SCHEDULES. | | | | 2)NOTE: PLEASE SEE THAT MEANS OF EGRESS | | LIGHTING CONTROL MUST ALSO HAVE A MEANS | | CONTROL FOR STAIRWAYLIGHTING FROM | | SECOND FLR. LS101 5-8 | | | | 3)NOTE: PLEASE SEE FIRE REVIEW NOTES AS | | THEY WILL HAVE A DIRECT AFFECT ON | | ELECTRICAL PLANS. | | | | 4)NOTE: PLEASE CLARIFYSERVICE, SHOWN | | AS NEW, BUT IF SERVICE EXSITING PLEASE | | NOTE AS EXISTING. | | | | 5)NOTE: PLEASE CLARIFY WORK SHOP, WHAT | | WILL BE THIS ROOM BE USED FOR. PLEASE | | SHOW ANY CLASS LOCATIONS, IF ANY. | | | | 6)NOTE; PLEASE SEE 600.5 , IF BLDG WILL | | HAVE ANY PUBLIC TRAFFIC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|