Plan Review Notes
Plan Review Notes For Permit 03121021
Permit Number 03121021
Review Stop E
Sequence Number 1
Notes
Date Text
2003-12-30 00:00:00*************** UNSAT ************
  
 1)NOTE: PLEASE CORRELATECIRCUITS #'S
 ON PLANS AND PANEL SCHEDULES.
  
 2)NOTE: PLEASE SEE THAT MEANS OF EGRESS
 LIGHTING CONTROL MUST ALSO HAVE A MEANS
 CONTROL FOR STAIRWAYLIGHTING FROM
 SECOND FLR. LS101 5-8
  
 3)NOTE: PLEASE SEE FIRE REVIEW NOTES AS
 THEY WILL HAVE A DIRECT AFFECT ON
 ELECTRICAL PLANS.
  
 4)NOTE: PLEASE CLARIFYSERVICE, SHOWN
 AS NEW, BUT IF SERVICE EXSITING PLEASE
 NOTE AS EXISTING.
  
 5)NOTE: PLEASE CLARIFY WORK SHOP, WHAT
 WILL BE THIS ROOM BE USED FOR. PLEASE
 SHOW ANY CLASS LOCATIONS, IF ANY.
  
 6)NOTE; PLEASE SEE 600.5 , IF BLDG WILL
 HAVE ANY PUBLIC TRAFFIC.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  