Plan Review Notes
Plan Review Notes For Permit 03121021
Permit Number 03121021
Review Stop B
Sequence Number 1
Notes
Date Text
2004-01-14 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03121021
 ADD: 1016 CLARE AVE
 CONT: SPRADLEY CONST
 TEL: (561)301-1004
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST BUILDING REVIEW
 ACTION: DENIED
  
 1)FL BLD CODE 104.2.1.2
 ADDITIONAL INFORMATION REQUIRED,
 4HR RATED WALL BETWEEN UNITS 4 & 5. THE
 PLANS INDICATE THE USE OF ROLL UP DOOR?
 EXPLAINOR PROVIDE RATING ON DOOR?
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) GLASS BLOCK, WALL THICKNESS MAY
 REQUIRE STORM SHUTTERS.
 B) NEW ROLL UP DOOR.
 C) NEW STOREFRONT GLASS
 D) TELLAR STYLE STEEL DOOR
  
 3)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4)11-4.8.2 SLOPE & RISE. THE LEAST
 POSSIBLE SLOPE SHALL BE USED FOR ANY
 RAMP. THE MAXIMUM SLOPE FOR A RAMP IN
 NEW CONSTRUCTION SHALL BE 1 TO 12. THE
 MAXIMUM RISE FOR RUN SHALL BE 30" (SEE
 FIGURE 16).
  
 5)11-4.8.4.(2) LANDINGS. ALL LANDINGS
 ON RAMPS SHALL NOT BE LESS THAN 60"
 CLEAR, & THE BOTTOM OF EACH RAMP SHALL
 HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARENCE.
  
 6)11.4.8.5. HANDRAILS: IF A RAMP HAS
 A RISE GREATER THAN 6" OR A HORIZONTAL
 PROJECTION GREATER THAN 72", THEN IT
 SHALL HAVE HANDRAILS ON BOTH SIDES.
  
 7)1204.2 SURROUNDING MATERIALS;
 THE WALLS & FLOORS OF ALL PUBLIC REST-
 ROOMS SHALL BE LINED WITH NONABSORBANT
 MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE
 FLOOR.
  
 8) PLANS INDICATE A SECOND AND THIRD
 FLOOR, PLEASAE HOW EXITING.
  
 9) 1016.2.1 EMERGENCY LIGHTING , PROVIDE
 LAYOUT SHOWING STORAGE AREAS AND EGRESS
 ROUTES, PLANS INDICATE A THIRD FLOOR BUT
 NO INFORMATION PROVIDED.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026