2004-01-14 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03121021 |
| ADD: 1016 CLARE AVE |
| CONT: SPRADLEY CONST |
| TEL: (561)301-1004 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 1ST BUILDING REVIEW |
| ACTION: DENIED |
| |
| 1)FL BLD CODE 104.2.1.2 |
| ADDITIONAL INFORMATION REQUIRED, |
| 4HR RATED WALL BETWEEN UNITS 4 & 5. THE |
| PLANS INDICATE THE USE OF ROLL UP DOOR? |
| EXPLAINOR PROVIDE RATING ON DOOR? |
| |
| 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) GLASS BLOCK, WALL THICKNESS MAY |
| REQUIRE STORM SHUTTERS. |
| B) NEW ROLL UP DOOR. |
| C) NEW STOREFRONT GLASS |
| D) TELLAR STYLE STEEL DOOR |
| |
| 3)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 4)11-4.8.2 SLOPE & RISE. THE LEAST |
| POSSIBLE SLOPE SHALL BE USED FOR ANY |
| RAMP. THE MAXIMUM SLOPE FOR A RAMP IN |
| NEW CONSTRUCTION SHALL BE 1 TO 12. THE |
| MAXIMUM RISE FOR RUN SHALL BE 30" (SEE |
| FIGURE 16). |
| |
| 5)11-4.8.4.(2) LANDINGS. ALL LANDINGS |
| ON RAMPS SHALL NOT BE LESS THAN 60" |
| CLEAR, & THE BOTTOM OF EACH RAMP SHALL |
| HAVE NOT LESS THAN 72" OF STRAIGHT & |
| LEVEL CLEARENCE. |
| |
| 6)11.4.8.5. HANDRAILS: IF A RAMP HAS |
| A RISE GREATER THAN 6" OR A HORIZONTAL |
| PROJECTION GREATER THAN 72", THEN IT |
| SHALL HAVE HANDRAILS ON BOTH SIDES. |
| |
| 7)1204.2 SURROUNDING MATERIALS; |
| THE WALLS & FLOORS OF ALL PUBLIC REST- |
| ROOMS SHALL BE LINED WITH NONABSORBANT |
| MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| FLOOR. |
| |
| 8) PLANS INDICATE A SECOND AND THIRD |
| FLOOR, PLEASAE HOW EXITING. |
| |
| 9) 1016.2.1 EMERGENCY LIGHTING , PROVIDE |
| LAYOUT SHOWING STORAGE AREAS AND EGRESS |
| ROUTES, PLANS INDICATE A THIRD FLOOR BUT |
| NO INFORMATION PROVIDED. |
| |