Plan Review Notes
Plan Review Notes For Permit 03120934
Permit Number 03120934
Review Stop P
Sequence Number 2
Notes
Date Text
2004-02-23 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 A) COMMENTS FROM PREVIOUS REVIEW HAVE
 NOT BEEN ADDRESSED SUFFICIENTLY. COMMENT
 NUMBERS SHALL REMAIN THE SAME FOR CLAIR-
 ITY.
 3) SHT A3 (CHANGED FROM A2) FLOOOR PLAN
 URINAL SHALL BE ACCESSIBLE PER SECTION
 11-4.22.5. PROVIDE A DETAIL SHOWING
 COMPLIANCE WITH SECTION 11-4.18 AND ALL
 SUBSECTIONS.
 4) PROVIDE A ROOF PLAN. SHOW PRIMARY AND
 SECONDARY ROOF DRAINS AND THEIR LOCATION
 AND SHOW SIZE OF DRAINS AND PIPE SIZES.
 5) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 & 1107 AND ALL SUBSECTIONS. SHOW 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADDED TO CLACULATIONS. SHOW
 AREAS OF ROOFS THAT DRAIN ONTO ROOF FROM
 ABOVE ADDED TO CALCULATIONS.
 ----------NO DETAIL WAS SUBMITTED FOR
 THE URNAL---------NO CALCULATIONS SHOW-
 ING 1/2 AREA OF VERTICAL WALLS ADDED TO
 SQUARE FOOTAGE OF ROOF. NO AREA OF UPPER
 ROOF WAS SHOWN BEING ADDED TO CALCULAT-
 IONS. NO PRIMARY ROOF DRAINS ARE SHOWN.
 ONLY SCUPPER DRAINS WERE SHOWN. (SECOND-
 ARY DRAINS) - NO NEW SECTION OF ROOF IS
 SHOWN BEING ADDED TO EXISTING ROOF.-----
 NEW COMMENT********
 1B) SUBMIT A DETAIL SHOWING ALL SECOND-
 ARY SCUPPERS SHOWING HEIGHT & WIDTH AND
 SHOW HEIGHT OF FLOW LINE OFF ROOF AS RE-
 QUIRED IN SECTION 1503.4.2 OF THE FBC
 BUILDING.
 2B) REFERENCED ON SHEET A10 IS TABLE
 1106.3 FOR HORIZONTAL PIPING. NO PIPING
 IS SHOWN. SUBMIT A STORM RISER DIAGRAM.
 3B) REFERENCED ON SHEET A10 IS TABLE
 1106.6 INDICATING THAT GUTTERS ARE BEING
 USED. NO GUTTERS ARE SHOWN. PLEASE
 CLAIRFY.
 4B) A CERTIFICATE OF AUTHORIZATION IS
 REQUIRED PER FS 481.219
 *******NEW COMMENTS
 5B) UPON CONVERSING WITH BLDG PLAN RE-
 VIEWER, I SEE THAT THERE ARE MODIFICAT-
 IONS TO THE OTHER BLDG. (SOUND ADVISE)
 THIS WILL REQUIRE CALCULATIONS FOR THE
 EXISTING ROOF OF THAT BLDG. SHOWING THE
 SQUARE FOOTAGE OF THE ROOF AND SHOWING
 1/2 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS. A ROOF PLAN WILL BE REQUIRED
 SHOWING PRIMARY AND SECONDARY ROOF
 DRAINS AND THERE LOCATION. SHOW SIZES OF
 ROOF DRAINS, PIPING SIZES, GUTTERS,
 RAIN WATER LEADERS, DOWNSPOUTS ECT.
 SECTIONS 1106 & 1107 AND ALL SUBSECTIONS
 6B) MSDS SHEETS FOR ALL HAZADOUS MATER-
 IALS. REVIEW OF THESE SHEETS MAY CAUSE
 MORE COMMENTS TO BE FORTHCOMMING. ALSO
 AN EYEWASH AND/OR EMERGENCY SHOWER MAY
 BE REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]