2004-03-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 03120934
 ADD: 2275 PALM BEACH LAKES BLVD
 CONT: HALLMARK BUILDERS
 TEL: (561)512-5517
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 2ND REVIEW
 ACTION: DENIED
  
 1) QUESTION# 1 FROM 1ST PLAN REVIEW:
 THE TYPES OF COMBUSTIBLE LIQUIDS PRO-
 VIDED FROM THE FIRST PLAN REVIEW MAY
 HAVE SOME DESCREPANCIES. PROVIDE THE MAN
 UFACTURES FLASH POINT AND BOILING POINTS
 FOR THE LIST PROVIDED. EXAMPLE CLEARCOAT
 LOOKS LIKE IT MAY BE A CLASS II WITHA
 BOILING POINT OF 104.INCLUDE THE BREAK
 DOWN FOR LACQUERS AND LACQUER THINNERS.
 ALSO PROVIDE THE MSDS SHEETS. ON MANY
 MSDS SHEETS THEY WILL REQUIRE A EYE WASH
  
 2) COMMENT# 2 FROM 1ST REVIEW, 407.1.3.5
 SPRAY BOOTHS SHALL BE PROTECTED BY AN
 AUTOMATIC SUPRESSION SYSTEM. A NOTE ON
 THE DRAWINGS DOESN'T MEET THE REQUIRE-
 MENTS OF THE CODE.
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS RQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 3) ONCE WE RECEIVE THE FLASH POINT AND
 BOILING POINT OF THE LIQUIDS TO BE
 STORED AND THE METHOD OF STORAGE (IF
 RATED FIRE CABINETS WILL BE REQUIRED)
 IF REQUIRED,SUBMIT CUT SHEETS, THEN THE
 OCCUPANCY WILL BE ASSIGNED.
 EXAMPLE; CLEARCOAT ON THE ENTERNET THIS
 LIQUID IS INDICATED AS A CLASS II LIQUID
 WITH A FLASH POINT OF 105.
 THE SECOND CONCERN IS TO PROVIDE
 MSDS SHEETS FOR THESE CHEMICALS, SOME
 CHEMICALS REQUIRE A EYE WASH FOR 15 MIN.
  
 4) THE NOTE INDICATING THE 2 HR RATING
 IS OK,BUT PROVIDE THE GA FILE DETAIL ON
 THE PLAN FOR THE INSPECTOR TO BE ABLE TO
 INSPECT BY.
  
 5)NOTE 5 FROM 1ST REVIEW, HAS BEEN
 PARTIALLY IGNORED.
 5A) THE FOAM TRIM CAN NOT BE USED IN THE
 FIRE DISTRICT. F102.7 ARCHITECTURAL TRIM
 ON BUILDINGS IN THE FIRE DISTRICT SHALL
 BE CONSTRUCTED OF NON-COMBUSTIBLE
 MATERIALS OR FIRE RETARDANT TREATED
 WOOD.
 5B) THE USE OF PLYWOOD FOR WALLS HAS
 BEEN DELETED FROM SOME PAGES,S3,S5 STILL
 HAVEDETAILS WITH THE USE OF WOOD AS WELL
 AS THE 3 MEMBER GIRDER IS A VERTICAL
 WALL SECTION!!!!!!
 5C) THE USE OF PLYWOOD HAS BEEN REMOVED
 FROM THE EXTERIOR TOWER WALL DIAPHRAM
 WHAT MATERIAL WILL MAKE THE WALL
 DIAPHRAM?
 5D) PLANS INDICATE ROOF SHEATHING ABOVE
 THE 35'-0" ELEVATION, ENG TO PROVIDE
 ATTACHMENT AND SPACING, REMEMBER ROOF
 ZONE #3 EDGE ZONES, NEGATIVE PRESSURES.
  
 7) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) GLAZED SWING DOORS
 B) GLAZED SWING DOORS W/ SIDELIGHTS
 C) GLAZED SWING DOORS W/ SIDELIGHTS &
 TRANSOMS
 D) MULLIONS, VERTICAL & HORIZONTAL
 E)WINDOWS
 F) STORM SHUTTERS IF IMPACT GLAZING IS
 NOT USED.
 G) LOUVERS
 H) EFIS- FOAM MOLDINGS
 I) ROOF ASSEMBLIES
 J) TRUSS ANCHORS
  
 8) ***********IMPORTANT***************
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 9) 1707.4.5.1 MULLIONS OCCURRING
 BETWEEN INDIVIDUAL WINDOW AND GLASS
 DOOR ASSEMBLIES. TESTING REPORTS ARE
 REQUIRED BY AN APPROVED TESTING
 LABORATORY OR BE ENGINEERED.
 PROVIDE PRODUCT TESTING REPORTS!!!!!!!!!
  
 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN-
 ED TO TRANSFER THE DESIGN PRESSURE LOADS
 APPLIED BY THE WINDOW OR DOOR ASSEMBLIES
 TO THE ROUGH OPENING SUBTRATE.
 PROVIDE PRODUCT TESTING REPORTS!!!!!!!
  
 11) COMMENT 16 FROM 1ST REVIEW: RETURN
 COMMENT SHEET INDICATES BOTTOM CHORD
 LIVE LOAD ADDED TO PLANS NO CLOUD OR
 DELTA INDICATING CHANGE? WHERE?
  
 12) PLANS INDICATE THE USE OF SEMCO
 STRAPS, REMOVE FROM PLANS!!!!! OUT OF
 BUSSINSS SINCE 1999! NO STATE APPROVALS
 ARE AVAILABLE.
 TRUSS ANCHOR SCHEDULE REMOVE THE WORD
 "SUBSTITUTE"
 104.2.1 W.P.B. ADMINISTRATIVE CODE
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR
 OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES.
 SUCH INFORMATION SHALL BE SPECIFIC
 AND THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE
 TERM "LEGAL" OR ITS EQUIVALENT BE USED
 AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION".
  
 13) ON THE SOUND ADVISE BUILDING HOW
 WILL THE NICHE BE ACHIEVED?
  
 14) ROOFS REQUIRE DRAINAGE, PROVIDE
 GUTTER SYSTEM THAT COMPLIES WITH SECTION
 1503.4.3 SIZING & DISCHARGE.
  
 15) 1503.4.4 PROTECTION AGAINST DECAY &
 TERMITES. CONDENSATE LINES & ROOF DOWN
 SPOUTS SHALL DISCHARGE AT LEAST 1 FT.
 AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EX-
 TENSIONS, OR SPLASH BLOCKS.
  
 16) A NEW NOTICE OF COMMENCEMENT MUST BE
 RECORDED. ONCE THE NOTICE OF COMMENCE-
 MENT IS RECORDED WORK MUST BE STARTED
 WITHIN 90 DAYS OR RERECORDED.
  
 17)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH
 THE PLANS WHEN RESUBMITTING PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN
 BE FOUND, WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
 JIM WITMER
 BUILDING PLAN REVIEW
 TEL: (561)805-6715
 FAX: (561)659-8026