2004-03-04 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 03120934 |
| ADD: 2275 PALM BEACH LAKES BLVD |
| CONT: HALLMARK BUILDERS |
| TEL: (561)512-5517 |
| FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| |
| 2ND REVIEW |
| ACTION: DENIED |
| |
| 1) QUESTION# 1 FROM 1ST PLAN REVIEW: |
| THE TYPES OF COMBUSTIBLE LIQUIDS PRO- |
| VIDED FROM THE FIRST PLAN REVIEW MAY |
| HAVE SOME DESCREPANCIES. PROVIDE THE MAN |
| UFACTURES FLASH POINT AND BOILING POINTS |
| FOR THE LIST PROVIDED. EXAMPLE CLEARCOAT |
| LOOKS LIKE IT MAY BE A CLASS II WITHA |
| BOILING POINT OF 104.INCLUDE THE BREAK |
| DOWN FOR LACQUERS AND LACQUER THINNERS. |
| ALSO PROVIDE THE MSDS SHEETS. ON MANY |
| MSDS SHEETS THEY WILL REQUIRE A EYE WASH |
| |
| 2) COMMENT# 2 FROM 1ST REVIEW, 407.1.3.5 |
| SPRAY BOOTHS SHALL BE PROTECTED BY AN |
| AUTOMATIC SUPRESSION SYSTEM. A NOTE ON |
| THE DRAWINGS DOESN'T MEET THE REQUIRE- |
| MENTS OF THE CODE. |
| 104.2.1 W.P.B. ADMINISTRATIVE CODE |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR |
| OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. |
| SUCH INFORMATION SHALL BE SPECIFIC |
| AND THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE |
| TERM "LEGAL" OR ITS RQUIVALENT BE USED |
| AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". |
| |
| 3) ONCE WE RECEIVE THE FLASH POINT AND |
| BOILING POINT OF THE LIQUIDS TO BE |
| STORED AND THE METHOD OF STORAGE (IF |
| RATED FIRE CABINETS WILL BE REQUIRED) |
| IF REQUIRED,SUBMIT CUT SHEETS, THEN THE |
| OCCUPANCY WILL BE ASSIGNED. |
| EXAMPLE; CLEARCOAT ON THE ENTERNET THIS |
| LIQUID IS INDICATED AS A CLASS II LIQUID |
| WITH A FLASH POINT OF 105. |
| THE SECOND CONCERN IS TO PROVIDE |
| MSDS SHEETS FOR THESE CHEMICALS, SOME |
| CHEMICALS REQUIRE A EYE WASH FOR 15 MIN. |
| |
| 4) THE NOTE INDICATING THE 2 HR RATING |
| IS OK,BUT PROVIDE THE GA FILE DETAIL ON |
| THE PLAN FOR THE INSPECTOR TO BE ABLE TO |
| INSPECT BY. |
| |
| 5)NOTE 5 FROM 1ST REVIEW, HAS BEEN |
| PARTIALLY IGNORED. |
| 5A) THE FOAM TRIM CAN NOT BE USED IN THE |
| FIRE DISTRICT. F102.7 ARCHITECTURAL TRIM |
| ON BUILDINGS IN THE FIRE DISTRICT SHALL |
| BE CONSTRUCTED OF NON-COMBUSTIBLE |
| MATERIALS OR FIRE RETARDANT TREATED |
| WOOD. |
| 5B) THE USE OF PLYWOOD FOR WALLS HAS |
| BEEN DELETED FROM SOME PAGES,S3,S5 STILL |
| HAVEDETAILS WITH THE USE OF WOOD AS WELL |
| AS THE 3 MEMBER GIRDER IS A VERTICAL |
| WALL SECTION!!!!!! |
| 5C) THE USE OF PLYWOOD HAS BEEN REMOVED |
| FROM THE EXTERIOR TOWER WALL DIAPHRAM |
| WHAT MATERIAL WILL MAKE THE WALL |
| DIAPHRAM? |
| 5D) PLANS INDICATE ROOF SHEATHING ABOVE |
| THE 35'-0" ELEVATION, ENG TO PROVIDE |
| ATTACHMENT AND SPACING, REMEMBER ROOF |
| ZONE #3 EDGE ZONES, NEGATIVE PRESSURES. |
| |
| 7) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) GLAZED SWING DOORS |
| B) GLAZED SWING DOORS W/ SIDELIGHTS |
| C) GLAZED SWING DOORS W/ SIDELIGHTS & |
| TRANSOMS |
| D) MULLIONS, VERTICAL & HORIZONTAL |
| E)WINDOWS |
| F) STORM SHUTTERS IF IMPACT GLAZING IS |
| NOT USED. |
| G) LOUVERS |
| H) EFIS- FOAM MOLDINGS |
| I) ROOF ASSEMBLIES |
| J) TRUSS ANCHORS |
| |
| 8) ***********IMPORTANT*************** |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 9) 1707.4.5.1 MULLIONS OCCURRING |
| BETWEEN INDIVIDUAL WINDOW AND GLASS |
| DOOR ASSEMBLIES. TESTING REPORTS ARE |
| REQUIRED BY AN APPROVED TESTING |
| LABORATORY OR BE ENGINEERED. |
| PROVIDE PRODUCT TESTING REPORTS!!!!!!!!! |
| |
| 10) 1707.4.5.2 MULLIONS SHALL BE DESIGN- |
| ED TO TRANSFER THE DESIGN PRESSURE LOADS |
| APPLIED BY THE WINDOW OR DOOR ASSEMBLIES |
| TO THE ROUGH OPENING SUBTRATE. |
| PROVIDE PRODUCT TESTING REPORTS!!!!!!! |
| |
| 11) COMMENT 16 FROM 1ST REVIEW: RETURN |
| COMMENT SHEET INDICATES BOTTOM CHORD |
| LIVE LOAD ADDED TO PLANS NO CLOUD OR |
| DELTA INDICATING CHANGE? WHERE? |
| |
| 12) PLANS INDICATE THE USE OF SEMCO |
| STRAPS, REMOVE FROM PLANS!!!!! OUT OF |
| BUSSINSS SINCE 1999! NO STATE APPROVALS |
| ARE AVAILABLE. |
| TRUSS ANCHOR SCHEDULE REMOVE THE WORD |
| "SUBSTITUTE" |
| 104.2.1 W.P.B. ADMINISTRATIVE CODE |
| DRAWINGS & SPECIFICATIONS SHALL CONTAIN |
| INFORMATION, IN THE FORM OF NOTES OR |
| OTHERWISE, AS TO THE QUALITY OF |
| MATERIALS, WHERE QUALITY IS ESSENTIAL TO |
| CONFORMITY WITH THE TECHNICAL CODES. |
| SUCH INFORMATION SHALL BE SPECIFIC |
| AND THE TECHNICAL CODES "SHALL NOT BE |
| CITED AS A WHOLE OR IN PART, NOR THE |
| TERM "LEGAL" OR ITS EQUIVALENT BE USED |
| AS A SUBSTITUTE FOR SPECIFIC |
| INFORMATION". |
| |
| 13) ON THE SOUND ADVISE BUILDING HOW |
| WILL THE NICHE BE ACHIEVED? |
| |
| 14) ROOFS REQUIRE DRAINAGE, PROVIDE |
| GUTTER SYSTEM THAT COMPLIES WITH SECTION |
| 1503.4.3 SIZING & DISCHARGE. |
| |
| 15) 1503.4.4 PROTECTION AGAINST DECAY & |
| TERMITES. CONDENSATE LINES & ROOF DOWN |
| SPOUTS SHALL DISCHARGE AT LEAST 1 FT. |
| AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EX- |
| TENSIONS, OR SPLASH BLOCKS. |
| |
| 16) A NEW NOTICE OF COMMENCEMENT MUST BE |
| RECORDED. ONCE THE NOTICE OF COMMENCE- |
| MENT IS RECORDED WORK MUST BE STARTED |
| WITHIN 90 DAYS OR RERECORDED. |
| |
| 17)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| LOOK FOR COMMENTS BY THE OTHER PLAN |
| REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| ON THE APPLICATION, PLANS, OR ATTACHED |
| SEPARATELY. WHEN RESUBMITTING PLANS |
| PLEASE CLEARLY INDICATE THE REVISION AND |
| REMOVE AND REPLACE ANY PAGES AS NECESS- |
| ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| THE PLANS WHEN RESUBMITTING PLANS. A |
| TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR |
| SPECIFICATION PAGE WHERE THE CHANGES CAN |
| BE FOUND, WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| JIM WITMER |
| BUILDING PLAN REVIEW |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |