Plan Review Notes
Plan Review Notes For Permit 03120934
Permit Number 03120934
Review Stop P
Sequence Number 1
Notes
Date Text
2004-01-09 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 11
  
 1) SHT A2 DEMO PLAN, ALL ABANDONED OR
 CAPPED PLUMBING LINES SHALL BE INSPECTED
 PRIOR TO COVERING.
 2) SHT A2 FLOOR PLAN, 11-4.22.2 DOORS
 SHALL NOT SWING INTO THE CLEAR FLOOR
 SPACE REQUIRED FOR ANY FIXTURE.
 3) SHT A2 FLOOR PLAN, URNAL SHALL BE
 ACCESSIBLE PER SECTION 11-4.22.5. PLEASE
 PROVIDE A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.18 AND ALL SUBSECTIONS.
 4) PROVIDE A ROOF PLAN SHOW PRIMARY AND
 SECONDARY ROOF DRAINS AND THEIR LOCATION
 AND SHOW SIZE OF DRAINS AND PIPE SIZES.
 5) SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106
 AND 1107 AND ALL SUBSECTIONS. SHOW 1/2
 AREA OF ALL VERTICAL WALLS INCLUDING
 PARAPETS ADDED TO CALCULATIONS. SHOW
 AREAS OF ROOFS THAT DRAIN ONTO ROOF FROM
 ABOVE ADDED TO CALCULATIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]