Plan Review Notes For Permit 03120934 |
Permit Number |
03120934 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2004-01-09 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 11 | | | | 1) SHT A2 DEMO PLAN, ALL ABANDONED OR | | CAPPED PLUMBING LINES SHALL BE INSPECTED | | PRIOR TO COVERING. | | 2) SHT A2 FLOOR PLAN, 11-4.22.2 DOORS | | SHALL NOT SWING INTO THE CLEAR FLOOR | | SPACE REQUIRED FOR ANY FIXTURE. | | 3) SHT A2 FLOOR PLAN, URNAL SHALL BE | | ACCESSIBLE PER SECTION 11-4.22.5. PLEASE | | PROVIDE A DETAIL SHOWING COMPLIANCE WITH | | SECTION 11-4.18 AND ALL SUBSECTIONS. | | 4) PROVIDE A ROOF PLAN SHOW PRIMARY AND | | SECONDARY ROOF DRAINS AND THEIR LOCATION | | AND SHOW SIZE OF DRAINS AND PIPE SIZES. | | 5) SUBMIT CALCULATIONS FOR PRIMARY AND | | SECONDARY ROOF DRAINS PER SECTIONS 1106 | | AND 1107 AND ALL SUBSECTIONS. SHOW 1/2 | | AREA OF ALL VERTICAL WALLS INCLUDING | | PARAPETS ADDED TO CALCULATIONS. SHOW | | AREAS OF ROOFS THAT DRAIN ONTO ROOF FROM | | ABOVE ADDED TO CALCULATIONS. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|