2004-01-07 00:00:00DENIED:
 1.CU-1 LOCATED ON THE ROOF SHALL
 COMPLY WITH 2001 FBC 1511.7 FOR HEIGHT
 REQUIREMENT BEWTEEN THE ROOF SURFACE &
 THE BOTTOM OF THE SUPPORT RAIL (SEE
 ATTACHED).
  
 2.CONDENSATE SHALL DISCHARGE A MINIMUM
 OF 12" FROM THE BUILDING STRUCTURE PER
 2001 FBC 1503.4.4.
  
 3.PLEASE PROVIDE MANUFACTURER
 SUBMITTAL DATA FOR THE SPRAY/MIXING
 BOOTH AND VENTILATION DETAILS WITH
 PERMIT APPLLICATION.INDICATE DISTANCE
 BETWEEN EXHAUST TERMINATION AND PROPERTY
 LINES ADJACENT BUILDINGS AND FRESH AIR
 INTAKES.SHOW COMPLIANCE WITH NFPA 33,
 AND 2001 FBC(M) CHAPTER 5.SEE COMMENTS
 BY FIRE DEPT. AND BUILDING.
  